| Plan Review Notes For Permit 21010734 |
| Permit Number |
21010734 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-11-01 13:41:25 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | | | 1) PRODUCT APPROVAL INSTALLATION INSTRUCTIONS PROVIDED | | | FOR THE DOOR (17184.11) IS EXPIRED - PLEASE PROVIDE THE | | | UPDATED INSTALLATION INSTRUCTIONS (17184.11 R8) - | | | PLEASE PROVIDE THE PRODUCT APPROVAL FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS. | | | | | | 2) ROOF PRODUCT APPROVAL FL35402 = ROOFING SYSTEM TO BE | | | USED ON THE PROVIDED PRODUCT APPROVAL REQUIRES | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONE 3 WHICH | | | REQUIRES A HIGHER PRESSURE (-79.06 PER DRAWING A2.2) | | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-67.5) | | | - SEE NOTE NUMBER 9 ON THE PRODUCT APPROVAL. | | | | | | | | | | | | | | | |
|