2021-07-21 09:15:531) MECHANICAL DESIGN MUST BE DRAWN BY EITHER A LICENSED
 ENGINEER, THE ARCHITECT OR THE MECHANICAL CONTRACTOR
 THAT HOLDS THE PERMIT TO INSTALL THE MECHANICAL SYSTEM
 FOR THIS PROJECT.
 2) I STILL DO NOT SEE THE ENERGY CALCULATIONS.
 3) I STILL DO NOT SEE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. THESE ALSO MUST BE DESIGNED BY A LICENSED
 ENGINEER, THE ARCHITECT OR THE MECHANICAL CONTRACTOR
 THAT HOLDS THE PERMIT TO INSTALL THE MECHANICAL SYSTEM
 FOR THIS PROJECT. FS 471.003(H)
  