| Date |
Text |
| 2021-02-10 08:30:02 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21010734 |
| | 2/10/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET S-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | WATER HEATER INDICATING MAKE, MODEL, GALLON SIZE, AND |
| | EFFICIENCY RATING- TABLE C404.2 FBC EC. SUBMIT AN |
| | ENERGY COMPLIANCE REPORT FOR THE NEW RESIDENCE AND |
| | INCLUDE THE WATER HEATER DATA IN THE REPORT- SECTION |
| | R101.5 FBC EC. PLEASE NOTE COMPLETE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE WATER HEATER CAN BE SUBMITTED |
| | FOR REVIEW OR SHALL BE ONSITE WITH THE INSTALLATION |
| | MANUAL AT TIME OF INSPECTION- SECTION 107.2.1 WPB. |
| | |
| | 2) S1 SANITARY RISER: A) SHOW ALL FIXTURE DRAIN SIZES- |
| | TABLE P3201.7 FBC RES. B) SHOW THE WASHING MACHINE |
| | STANDPIPE SIZE AND THE CONNECTING VERTICAL STACK SIZE- |
| | TABLE P3201.7 FBC RES, AND SECTION 406.2 FBC P. |
| | |
| | 3) A-1, S-1: SHOW THE LOCATIONS OF THE WATER SUPPLY |
| | SHUTOFF VALVES TO THE NEW WASHING MACHINE TO VERIFY |
| | ACCESS WILL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | P2903.9.3 FBC RES. |
| | |
| | 4) S1: SHOW THE LOCATIONS OF THE POTABLE WATER SUPPLY |
| | LINE ENTRANCE AND MAIN SHUTOFF VALVE- SECTIONS P2901.1, |
| | P2903.1, & P2903.9.1 FBC RES. |
| | |
| | 5) PLEASE NOTE THAT SEPARATE PERMITS AND PLANS ARE |
| | REQUIRED FOR THE POTABLE WATER BACKFLOW PREVENTER, GAS |
| | PIPING, AND IRRIGATION SYSTEMS- SECTION 105.1 & SECTION |
| | 107.2.1 WPB. |
| | |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |