| Plan Review Notes For Permit 21010734 |
| Permit Number |
21010734 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-02-10 15:33:08 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SMOKE ALARM MISSING ON THE OUTSIDE OF THE BEDROOMS. | | | | | | 2) SHOW LOCATION OF PANEL, AND ADD NOTE FOR SUBFEED TO | | | PANEL MUST BE UNDERGROUND OR A MAIN WILL BE REQIRED | | | OUTSIDE BY THE METER. |
|