| 2021-02-03 16:09:56 | 02/03/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW |
| | THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS. |
| | THE CALCULATIONS SHOW FILTER, CHLORINATOR PIPES, VALES, |
| | BUT THE HEATER IS NOT ON FRICTION LOSS ASSOCIATED WITH |
| | THESE ITEMS. PLEASE CORRECT PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 2. PLEASE IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS |
| | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS |
| | IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE |
| | TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. |
| | 4.4.9, 4.4.9.1. |
| | |
| | 3. PLEASE SUBMIT SPECIFICATIONS FOR THE CARTRIDGE |
| | FILTER PER THE WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 4. THE CITY OF WEST PALM BEACH HAS NO RECORD OF A GAS |
| | HEATER, BUT IT ONLY HAS A GAS GENERATOR. THIS COMMENT |
| | IS DIRECTED TO THE CONTRACTOR TO FOLLOW UP ON THE |
| | PROPER PERMIT, WHICH MAY INCUR ADDITIONAL PERMIT AND |
| | FEE AT THE HOMEOWNER EXPENSE PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 105.1. |
| | |
| | 5. SOLAR COVER REQUIRED PER 2017 FBC RE 403.10.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |