| 2021-03-02 10:20:53 | PLAN REVIEW / MECHANICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 / 1&2 FAMILY - SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PLAN SHEET 01 SHOWS MINI SPLIT C/U LOCATED AT REAR |
| | OF STRUCTURE. PLAN SHEET E-1 SHOWS TWO C/U'S. PLEASE |
| | CLARIFY? |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. SERVICE OUTLET REQUIRED AT MECH. EQUIPMENT. |
| | E3901.12 HVAC OUTLET. |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) |
| | OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED |
| | TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING |
| | MEANS. (210.63) |
| | |
| | 3. PROVIDE A CONDENSATE DISPOSAL PLAN- FBC R M1411.3 |
| | M1411.3 CONDENSATE DISPOSAL. |
| | CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE |
| | CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE |
| | OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM |
| | HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT |
| | LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO |
| | A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A |
| | NUISANCE. |
| | |
| | |
| | 4. TIE DOWN |
| | M1401.4EXTERIOR INSTALLATIONS. |
| | EQUIPMENT AND APPLIANCES INSTALLED OUTDOORS SHALL BE |
| | LISTED AND LABELED FOR OUTDOOR INSTALLATION. SUPPORTS |
| | AND FOUNDATIONS SHALL PREVENT EXCESSIVE VIBRATION, |
| | SETTLEMENT OR MOVEMENT OF THE EQUIPMENT. SUPPORTS AND |
| | FOUNDATIONS SHALL BE IN ACCORDANCE WITH SECTION |
| | M1305.1.4.1. |
| | |
| | 5. M1411.8 LOCKING ACCESS PORT CAPS. |
| | REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL |
| | BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR |
| | SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED |
| | ACCESS. |
| | A NOTE ON PLAN WILL SUFFICE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |