2021-02-03 10:58:21CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET G-102 (GENERAL ELECTRICAL NOTE 1): PLEASE
 CHANGE TO COMPLY WITH FBC 2020 7TH EDITION AND NEC
 2017.
 2) SHEET E101 (ONE-LINE DIAGRAM): MAXIMUM PRIMARY
 OVERCURRENT PROTECTION FOR TRANSFORMER MT-5 SHOULD BE
 50 AMPS. PLEASE CORRECT. NEC 450(3)(B), NEC 240.4
 3) PLEASE SUBMIT PANELS SCHEDULES FOR PDP-3A, PP-5, AND
 LP-3 FBC 107
 4) PLEASE SPECIFY AVAILABLE SHORT CIRCUIT CURRENTS AT
 MDS AND PANELS FBC 107
 5) SHEET E-103 (MAINS SWITCHBOARD ROOM): PLEASE SHOW
 DISTANCES FROM MDS TO WALLS TO SHOW COMPLIANCE WITH NEC
 110.26(C)(2)
 6) PLEASE SEE SIGNATURE COMMENTS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  