Plan Review Notes
Plan Review Notes For Permit 21010688
Permit Number 21010688
Review Stop E
Sequence Number 1
Notes
Date Text
2021-02-05 15:46:15CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET GC-002, GENERAL ELECTRICAL NOTES (NOTE 1):
 PLEASE MODIFY TO REFLECT EXISTING CURRENT CODES IN
 EFFECT FBC 2020 7TH EDITION, NEC 2017).
 2) PLEASE PROVIDE UPDATED AVAILABLE SHORT CIRCUIT
 CURRENT (AIC) AT SERVICE LOCATION (FPL LETTER)
 3) SHEET E-001 AND E-004: RISER DIAGRAM ON E-001
 SPECIFIES SIX SETS OF 4#500 KCMIL + 1#1/0 G FROM ATS TO
 MSB WHILE E-004 (MSB SCHEDULE) SHOWS 6 SETS OF 4#600
 MCM + 1#1/0 GND. PLEASE CORRECT DISCREPANCIES. FBC 107
 4) SHEET E-004 (MSB CKT 32,34,36 FOR LIFT STATION).
 BREAKER IS 60 AMPS AND CONDUCTOR IS #8 WITH AMPACITY OF
 50 AMPS. PLEASE INCREASE CONDUCTOR SIZE.
 5) SEE SIGNATURE COMMENTS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  