| 2022-01-04 15:50:02 | FAILED |
| | |
| | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| | PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO |
| | THIS PERMIT BEING APPROVED. SOME OF THE COMMENTS BELOW |
| | ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS WELL AS |
| | WITH THIS PERMIT. |
| | |
| | 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| | THE POLE COLOR IS TO MATCH THE EXISTING DECORATIVE CITY |
| | LIGHT POLES (SPECKLED CONCRETE) LOCATED ON SOUTH |
| | FLAGLER DRIVE AND EVERNIA STREET. |
| | |
| | 3) THE POLE LOCATION IS APPROVED BY THE SPECIAL EVENTS; |
| | HOWEVER, ADDITIONAL INFORMATION CLARITY IS REQUIRED SO |
| | PLANNING STAFF CAN VERIFY THAT THERE IS PROPER ADA |
| | CLEARANCE BETWEEN THE POLE AND THE EDGE OF THE |
| | SIDEWALK: |
| | |
| | A. STAFF HAS REVIEWED THE RAYCAP POLE DESIGN |
| | INFORMATION THAT WAS PROVIDED, AND IT SHOWS A 14-INCH |
| | DIAMETER POLE MOUNTED ON A 16-INCH OUTSIDE DIMENSION |
| | BASE PLATE. THE BASE PLATE SETS THE WIDTH OF THE ABOVE |
| | GROUND FACILITY AT GRADE. SHEET C-3 SHOWS THE CAISSON |
| | EXTENDING 8-INCHES PAST THE EDGE OF THE POLE, WHICH IS |
| | 7-INCHES PAST THE EDGE OF THE BASE PLATE. |
| | |
| | B. THE SURVEY MUST CLEARLY SHOW THE DIMENSION FROM THE |
| | INSIDE EDGE OF THE CURB TO THE RIGHT-OF-WAY LINE AND |
| | THE DIMENSION FROM THE INSIDE EDGE OF THE CURB FOR THE |
| | WIDTH OF THE SIDEWALK. THE 6-INCH CURB MAY NOT BE |
| | INCLUDED IN THIS MEASURE, SINCE THE 6-INCH CURB IS NOT |
| | CONSIDERED A FLUSH SURFACE AND MAY NOT BE USED TO MEET |
| | THE REQUIRED ADA MINIMUM SIDEWALK WIDTH OF 36-INCHES. |
| | |
| | C. BASED ON THE INFORMATION THAT IS REQUIRED ON THE |
| | SURVEY AND THE POLE SPECIFICATIONS, STAFF WILL VERIFY |
| | THAT THERE IS ADA SIDEWALK CLEARANCE. NOTE: IF THE |
| | CAISSON IS INSTALLED AT THE EDGE OF THE RIGHT-OF-WAY, |
| | THEN THE BASE PLATE EXTENDS 23-INCHES FROM THE |
| | RIGHT-OF-WAY LINE AND INTO THE SIDEWALK. IN ORDER TO |
| | HAVE THE 36-INCH CLEARANCE, THE WIDTH FROM THE INSIDE |
| | EDGE OF THE CURB TO THE RIGHT-OF-WAY LINE MUST BE SHOWN |
| | ON THE SURVEY AS AT LEAST 59-INCHES OR 4.92-FEET. |
| | |
| | 4) FROM THE INFORMATION PRESENTED, THE 14-INCH DIAMETER |
| | POLE DOES NOT FIT AT THIS LOCATION. |
| | |
| | 5) THE COMMUNICATION FACILITY PLACEMENT PERMIT - CITY |
| | RIGHTS-OF-WAY SHOWS THE UNDERGROUND ELECTRIC BEING |
| | SUPPLIED FROM AN FPL TRANSFORMER THAT IS LOCATED ON |
| | CITY PROPERTY ON THE EAST SIDE OF EVERNIA STREET. THE |
| | SURVEY NEEDS TO SHOW THAT THE AREA WHERE YOU PLAN TO |
| | PULL POWER FROM ACROSS CITY PROPERTY IS LOCATED WITHIN |
| | A UTILITY EASEMENT. IF NO EASEMENT IS PRESENT, YOU WILL |
| | NEED TO GET THE POWER FROM AN ALTERNATIVE LOCATION. THE |
| | UNDERGROUND ELECTRIC PLANS MUST BE INCLUDED WITH THE |
| | ELECTRIC PERMIT 21010664. |
| | |