Plan Review Notes
Plan Review Notes For Permit 21010664
Permit Number 21010664
Review Stop Z
Sequence Number 2
Notes
Date Text
2021-05-25 14:28:54FAILED
  
 PRIOR TO ZONING APPROVAL OF THIS PERMIT, YOU ARE
 REQUIRED TO HAVE AN ISSUED COMMUNICATION FACILITY
 PLACEMENT PERMIT - CITY RIGHTS-OF-WAY. THE PLANS
 INCLUDED WITH THIS ELECTRICAL PERMIT MUST MATCH THE
 PLANS APPROVED WITH THE AFOREMENTIONED PERMIT. THE
 COMMENTS BELOW WHERE PROVIDED AS PART OF THE
 COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY AND APPLY FOR THE ECLECTIC PERMIT
 SUBMITTAL.
  
 1) THE COVER SHEET "SCOPE OF WORK" CALLS OUT THAT THERE
 WILL BE AN ENCLOSURE CABINET. THIS POLE IS APPROVED TO
 BE A STEALTH POLE, WHICH DOES NOT PERMIT AN ENCLOSURE
 CABINET MOUNTED TO IT.
  
 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR IS TO MATCH THE EXISTING DECORATIVE CITY
 LIGHT POLES (SPECKLED CONCRETE) LOCATED ON SOUTH
 FLAGLER DRIVE AND EVERNIA STREET.
  
 3) THE POLE LOCATION IS APPROVED BY THE SPECIAL EVENTS;
 HOWEVER, THERE IS ARE DISCREPANCIES BETWEEN THE SURVEY
 AND SITE PLAN AND THE EQUIPMENT PLAN REGARDING THE POLE
 DIAMETER WHICH NEED TO BE CORRECTED SO PLANNING STAFF
 CAN VERIFY THAT THERE IS PROPER ADA CLEARANCE BETWEEN
 THE POLE AND THE EDGE OF PAVEMENT:
  
 A. THE STEALTH POLE SHOWN ON SHEET C3, ELEVATION AND
 EQUIPMENT PLAN, HAS A 14-INCH DIAMETER. THE SURVEY
 SHOWS A FOUR (4) INCH DIAMETER POLE. SHEET C2, SITE
 PLAN, DOES NOT CALL OUT THE DIAMETER OF THE POLE, BUT
 SEEMS TO MIRROR THE SURVEY.
  
 B. THE SURVEY AND THE SITE PLAN SHOW A SIDEWALK WIDTH
 OF FOUR (4) FEET PLUS A SIX (6) INCH CURB FOR A TOTAL
 OF 54 INCHES IN WIDTH. A 14-INCH DIAMETER POLE OFFSET 7
 INCHES FROM THE EDGE OF THE RIGHT-OF-WAY RESULTS IN THE
 OUTSIDE EDGE OF THE POLE BEING 33 INCHES FROM THE
 TRAVEL LANE NOT 43 INCHES AS LISTED ON THE SURVEY. ADA
 REQUIRES A 36-INCH-WIDE FLUSH SURFACE, WHICH YOU DO NOT
 HAVE AT 33 INCHES. NOTE: THE FULL SIX (6) INCH CURB IS
 NOT CONSIDERED A FLUSH SURFACE SINCE THE OUTSIDE
 PORTION OF THE CURB SLOPES INTO A ROUNDED CONDITION
 WHERE IT TRANSITIONS TO THE ROADSIDE FACE OF THE CURB,
 SO YOU HAVE EVEN LESS THAN 33 INCHES AT THIS LOCATION.
  
 4) FROM THE INFORMATION PRESENTED, THE 14-INCH DIAMETER
 POLE DOES NOT FIT AT THIS LOCATION.
  
 NOTE: A RIGHT-OF-WAY USE PERMIT FOR THE PLACEMENT OF
 THE POLE WITHIN THE RIGHTS-OF-WAY WILL BE REQUIRED
 PRIOR TO STARTING ANY WORK.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  