Plan Review Notes
Plan Review Notes For Permit 21010630
Permit Number 21010630
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-03 14:37:30SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION AND
 SIZES OF THE SHUTTERS TO BE INSTALLED. PLEASE SHOW THE
 DISTANCE FROM THE EDGE OF THE SHUTTER TO THE CORNER OF
 THE BUILDING FOR THE SHUTTERS NEAR THE CORNERS OF THE
 BUILDING.
 2) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE SHUTTERS (NEED FRONT
 PAGES AND THE INSTALLATION INSTRUCTIONS).
 3) COMPLETE THE FORM PROVIDED AT THE FRONT COUNTER
 "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES" OR PROVIDE ALL INFORMATION
 REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET)
 - WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). FORMS CAN
 BE PROVIDED BY EMAILING [email protected] AND ASKING FOR
 "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES? FORM.
 4) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - PLEASE REVISE THE BUILDING PERMIT
 APPLICATION TO SHOW THE CORRECT JOB VALUE - JOB VALUE
 NEEDS TO BE THE COST OF THE SHUTTERS + THE COST TO
 INSTALL THE SHUTTERS AS IF A CONTRACTOR BID THE JOB.