2021-02-10 17:17:031ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21010619
 2/10/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 NFPA 58- 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E.01: SHOW THE LOCATION OF THE 1ST STAGE
 REGULATOR AND SHUTOFF VALVE AT THE TANK- SECTION 6.8.1
 NFPA- 58.
  
 2) SHOW THE BURIAL DEPTH OF THE LP PIPING AND INDICATE
 A TRACER WIRE WILL BE INSTALLED- SECTION 6.9.4 &
 6.9.4.6 NFPA 58.
  
 3) E.01: SHOW THE FLEX CONNECTOR AT THE GENERATOR AND
 SUBMIT MANUFACTURER?S SPECIFICATION- SECTION 6.9.6
 NFPA-58, AND SECTION G2422.1 FBC RES.
  
 4) E.01: CORRECT THE GENERATOR BTUH LOAD TO INDICATE
 355,000 BTU BASED ON THE SUBMITTED SPECS- SECTION
 G2408.1 FBC RES.
  
 5) THE SUBMITTED PIPE SIZING TABLE FROM 2011 IS
 OUTDATED. PLEASE SUBMIT THE UPDATED TABLE SIZING TABLE
 FROM THE NFPA 58- 2014.
  
 6) E.01: & SURVEY: SHOW THE CLEARANCE DISTANCE
 MEASUREMENTS FROM THE GENERATOR TO MECHANICAL AND
 GRAVITY AIR INTAKES INCLUDING OPERABLE WINDOWS AND
 DOORS INTO THE BUILDING- SECTION R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  