| 2021-02-10 17:17:03 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21010619 |
| | 2/10/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | NFPA 58- 2014 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET E.01: SHOW THE LOCATION OF THE 1ST STAGE |
| | REGULATOR AND SHUTOFF VALVE AT THE TANK- SECTION 6.8.1 |
| | NFPA- 58. |
| | |
| | 2) SHOW THE BURIAL DEPTH OF THE LP PIPING AND INDICATE |
| | A TRACER WIRE WILL BE INSTALLED- SECTION 6.9.4 & |
| | 6.9.4.6 NFPA 58. |
| | |
| | 3) E.01: SHOW THE FLEX CONNECTOR AT THE GENERATOR AND |
| | SUBMIT MANUFACTURER?S SPECIFICATION- SECTION 6.9.6 |
| | NFPA-58, AND SECTION G2422.1 FBC RES. |
| | |
| | 4) E.01: CORRECT THE GENERATOR BTUH LOAD TO INDICATE |
| | 355,000 BTU BASED ON THE SUBMITTED SPECS- SECTION |
| | G2408.1 FBC RES. |
| | |
| | 5) THE SUBMITTED PIPE SIZING TABLE FROM 2011 IS |
| | OUTDATED. PLEASE SUBMIT THE UPDATED TABLE SIZING TABLE |
| | FROM THE NFPA 58- 2014. |
| | |
| | 6) E.01: & SURVEY: SHOW THE CLEARANCE DISTANCE |
| | MEASUREMENTS FROM THE GENERATOR TO MECHANICAL AND |
| | GRAVITY AIR INTAKES INCLUDING OPERABLE WINDOWS AND |
| | DOORS INTO THE BUILDING- SECTION R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |