| 2021-02-04 13:24:46 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21010603 |
| | 2/4/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE NOTE THAT SEPARATE PERMITS AND PLANS ARE |
| | REQUIRED FOR: |
| | A) GAS PIPING FOR THE POOL HEATER. |
| | B) MAKEUP WATER RPZ BACKFLOW PREVENTER. |
| | C) PLUMBING PIPING FOR REQUIRED POOL PLUMBING FIXTURES, |
| | POOL DECK DRAINS, EQUIPMENT ROOM FLOOR DRAIN, AND HOSE |
| | BIBS. |
| | D) EQUIPMENT ROOM CONSTRUCTION, ACCESS, AND |
| | VENTILATION. |
| | |
| | 2) PLEASE ADD THE APPLICABLE ANSI/APSP DESIGN STANDARDS |
| | IN THE CODE NOTES- SECTION 107.2.1 WPB. |
| | |
| | 3) SHEETS 1: SHOW THE LOCATIONS OF THE REQUIRED HOSE |
| | BIBS FOR THE EQUIPMENT ROOM AND RESTROOMS- SECTIONS |
| | 454.1.5.9 & 454.1.6.1.4 FBC B. VERIFY THE HOSE BIBS |
| | WILL BE EQUIPPED WITH VACUUM BREAKERS TO PREVENT |
| | CROSS-CONNECTION- SECTION 454.1.6.3. PLEASE SEE |
| | SECTIONS 608.9 AND 608.9.1 FBC P AND INDICATE SIGNAGE |
| | WILL BE PROVIDED FOR THE HOSE BIBS THAT READS: |
| | ?NONPOTABLE WATER IS UTILIZED FOR [APPLICATION NAME]. |
| | CAUTION: NONPOTABLE WATER "DO NOT DRINK." |
| | |
| | 4) SHEET 1: MODIFY THE NOTE AT THE COLLECTOR TANK TO |
| | INDICATE ONE FLOOR BELOW. THE TANK SHALL BE LOCATED IN |
| | A ROOM OR AN ENCLOSURE. PROVIDE DETAILS IN ACCORDANCE |
| | WITH SECTION 454.1.5.1 AND INDICATE HOW ACCESS WILL BE |
| | PROVIDED TO THE TANK- SECTION 454.1.5.5 FBC B. |
| | |
| | 5) SHEET 2: PLEASE MODIFY THE WALL RETURN NOTE TO |
| | INDICATE THE LEVEL LOCATIONS OF THE INLETS- SECTION |
| | 454.1.6.5.9 FBC B. |
| | |
| | 6) SHEET 2: THE MAIN FLOOR DRAIN IS MISLABELED AS WALL |
| | MOUNTED ON THE POOL PIPING PLAN- SECTION 454.1.6.5.10 |
| | FBC B. |
| | |
| | 7) SHEET 1 & 2: PROVIDE TOTAL DYNAMIC HEAD CALCULATIONS |
| | FOR SIZING OF THE PUMP AND FLOW RATE OF THE SYSTEM- |
| | SECTIONS 454.1.6.5.4 AND 454.1.6.5.8 FBC B. |
| | |
| | 8) SHEETS 1 & 3: VERIFY THE CAPACITY OF THE COLLECTOR |
| | TANK SHALL BE SIZED FOR AT LEAST 1 MINUTE OF THE |
| | RECIRCULATED FLOW UNLESS JUSTIFIED BY THE DESIGN |
| | ENGINEER- SECTION 454.1.6.5.10.5 FBC B. |
| | |
| | 9) SHEETS 2 & 3: INDICATE HOW POOL WASTE WATER WILL BE |
| | DISPOSED OF- SECTION 454.1.6.5.15 |
| | |
| | 10) SHEETS 2 & 3: PLEASE NOTE THAT THE APPROVED |
| | BUILDING PLANS UNDER PERMIT 20011267 SHOW AN 1-1/2 IN. |
| | MAKEUP WATER LINE (SHEET P6-01), AND A 250 CFH POOL |
| | HEATER (P6-03). |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |