2021-02-04 13:24:461ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21010603
 2/4/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THAT SEPARATE PERMITS AND PLANS ARE
 REQUIRED FOR:
 A) GAS PIPING FOR THE POOL HEATER.
 B) MAKEUP WATER RPZ BACKFLOW PREVENTER.
 C) PLUMBING PIPING FOR REQUIRED POOL PLUMBING FIXTURES,
 POOL DECK DRAINS, EQUIPMENT ROOM FLOOR DRAIN, AND HOSE
 BIBS.
 D) EQUIPMENT ROOM CONSTRUCTION, ACCESS, AND
 VENTILATION.
  
 2) PLEASE ADD THE APPLICABLE ANSI/APSP DESIGN STANDARDS
 IN THE CODE NOTES- SECTION 107.2.1 WPB.
  
 3) SHEETS 1: SHOW THE LOCATIONS OF THE REQUIRED HOSE
 BIBS FOR THE EQUIPMENT ROOM AND RESTROOMS- SECTIONS
 454.1.5.9 & 454.1.6.1.4 FBC B. VERIFY THE HOSE BIBS
 WILL BE EQUIPPED WITH VACUUM BREAKERS TO PREVENT
 CROSS-CONNECTION- SECTION 454.1.6.3. PLEASE SEE
 SECTIONS 608.9 AND 608.9.1 FBC P AND INDICATE SIGNAGE
 WILL BE PROVIDED FOR THE HOSE BIBS THAT READS:
 ?NONPOTABLE WATER IS UTILIZED FOR [APPLICATION NAME].
 CAUTION: NONPOTABLE WATER "DO NOT DRINK."
  
 4) SHEET 1: MODIFY THE NOTE AT THE COLLECTOR TANK TO
 INDICATE ONE FLOOR BELOW. THE TANK SHALL BE LOCATED IN
 A ROOM OR AN ENCLOSURE. PROVIDE DETAILS IN ACCORDANCE
 WITH SECTION 454.1.5.1 AND INDICATE HOW ACCESS WILL BE
 PROVIDED TO THE TANK- SECTION 454.1.5.5 FBC B.
  
 5) SHEET 2: PLEASE MODIFY THE WALL RETURN NOTE TO
 INDICATE THE LEVEL LOCATIONS OF THE INLETS- SECTION
 454.1.6.5.9 FBC B.
  
 6) SHEET 2: THE MAIN FLOOR DRAIN IS MISLABELED AS WALL
 MOUNTED ON THE POOL PIPING PLAN- SECTION 454.1.6.5.10
 FBC B.
  
 7) SHEET 1 & 2: PROVIDE TOTAL DYNAMIC HEAD CALCULATIONS
 FOR SIZING OF THE PUMP AND FLOW RATE OF THE SYSTEM-
 SECTIONS 454.1.6.5.4 AND 454.1.6.5.8 FBC B.
  
 8) SHEETS 1 & 3: VERIFY THE CAPACITY OF THE COLLECTOR
 TANK SHALL BE SIZED FOR AT LEAST 1 MINUTE OF THE
 RECIRCULATED FLOW UNLESS JUSTIFIED BY THE DESIGN
 ENGINEER- SECTION 454.1.6.5.10.5 FBC B.
  
 9) SHEETS 2 & 3: INDICATE HOW POOL WASTE WATER WILL BE
 DISPOSED OF- SECTION 454.1.6.5.15
  
 10) SHEETS 2 & 3: PLEASE NOTE THAT THE APPROVED
 BUILDING PLANS UNDER PERMIT 20011267 SHOW AN 1-1/2 IN.
 MAKEUP WATER LINE (SHEET P6-01), AND A 250 CFH POOL
 HEATER (P6-03).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  