| 2021-02-01 10:30:46 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) PLEASE PROVIDE FULL LOAD CALCULATIONS FOR ENTIRE |
| | SERVICE INCLUDING EXISTING PANEL AND NEW TWO-STORY |
| | ACCESSORY STRUCTURE. FBC 107 |
| | 2) PLEASE SPECIFY SIZE OF NEW SERVICE LATERAL FBC 107 |
| | 3) UPPER ROOM: ALL BRANCH CIRCUITS THAT SUPPLY |
| | 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| | INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| | PROTECTED. PROVIDE CORRECTION. NEC 210.12; FBC RE |
| | E3902.16 (A NOTE WILL SUFFICE) |
| | 4) PLEASE SPECIFY AIC RATINGS OF NEW SERVICE AND PANELS |
| | FBC 107 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | ENRIQUE QUINONEZ |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |