| Plan Review Notes For Permit 21010590 |
| Permit Number |
21010590 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-07-09 09:55:01 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW THE EXTERIOR WALL SHEATHING THICKNESS | | | FBC R703.1.2 | | | 2) PLEASE SHOW THE EXTERIOR WALL SHEATHING ATTACHMENTS | | | (SIZE OF SCREWS OR NAILS) FBC R703.3.1 | | | 3) PLEASE PROVIDE MANUFACTURE SPECS SHOWING THE USE OF | | | "ZIP SYSTEM" AS FLOOR SHEATHING - FBC R503.1 | | | | | | | | | | | | | | | |
|