| 2021-01-27 09:05:33 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21010564 |
| | 1/27/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE DESCRIPTIONS OF WORK SHOWN ON THE APPLICATIONS |
| | STATING REPLACING THE SHOWER PAN DOES NOT MATCH THE |
| | PLAN WHICH SHOWS A TUB CONVERSION TO A SHOWER. PLEASE |
| | NOTE THAT THE CONDOMINIUM BUILDING AND BATHROOMS |
| | CONSTRUCTED UNDER PERMIT- 04110961 APPEAR TO BE HAVE |
| | BEEN CONSTRUCTED IN ACCORDANCE WITH THE FAIR HOUSING |
| | ACT AND THE GUIDELINES OF THE FAIR HOUSING ACT DESIGN |
| | MANUAL. PLEASE REFER TO PAGES 7.34- 7.59 OF THE MANUAL |
| | FOR REQUIRED TUB CONVERSION COMPLIANCE INFORMATION. |
| | |
| | BASED ON THE FLOOR PLAN IT APPEARS THAT THE MASTER BATH |
| | WAS CONSTRUCTED UNDER SPECIFICATION B BECAUSE OF THE |
| | FULL 30 X 48 IN. UNOBSTRUCTED CLEAR FLOOR SPACE |
| | PROVIDED FOR THE FIXTURE, AS OPPOSED TO THE OBSTRUCTED |
| | CLEAR FLOOR SPACE PROVIDED AT THE SHOWER IN THE COMMON |
| | BATHROOM- SEE EXAMPLES A & B ON PAGES 7.36 & 7.37. |
| | UNDER SPECIFICATION B WHICH REQUIRED ONLY ONE BATHROOM |
| | AND ONE BATHING FIXTURE TO MEET COMPLIANCE IN THE UNIT, |
| | THE NEW SHOWER SHALL BE IN COMPLIANCE UNDER |
| | SPECIFICATION B. PLEASE REFER TO PAGES 7.56- 7.59 AND |
| | REVISE THE DRAWINGS TO SHOW: |
| | |
| | A) LENGTH AND WIDTH DIMENSIONS OF THE NEW SHOWER. |
| | |
| | B) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | NEW SHOWER. |
| | |
| | C) REQUIRED GRAB BAR REINFORCEMENT AND REINFORCEMENT |
| | LOCATIONS AS INDICATED ON PAGE 7.56 AND THE FIGURES |
| | SHOWN ON PAGES 6.12 AND 6.13. |
| | |
| | AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE |
| | BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR |
| | THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED |
| | AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE |
| | PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE |
| | FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO |
| | REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO |
| | COMPLIANCE AT TIME OF SALE IF REQUESTED BY THE BUYER. |
| | IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO |
| | [email protected] AND I WILL SEND A COPY OF THE FAIR |
| | HOUSING AFFIDAVIT. |
| | |
| | 2) PROVIDE A SHOWER PAN DETAIL ION COMPLIANCE WITH |
| | SECTION 421.5.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |