| 2021-01-26 14:16:42 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21010518 |
| | ADD: 2600 N. FLAGLER DR. SUITE: 907 |
| | CONT: CLEANING SPECIALIST INC. |
| | TEL: 561-881-8784 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 26TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) THE CONTRACTOR NAME ON THE PERMIT APPLICATION DOES |
| | NOT MATH THE CONTRACTOR CGC NUMBER. TO LIST THIS OTHER |
| | BUSINESS NAME (SERV PRO OF NORTH PALM BEACH), YOU MUST |
| | REGISTER THIS DBA WITH THE STATE LICENSING BOARD, DBPR |
| | THEN AFTER REGISTERED WITH THE STATE REGISTER THE NEW |
| | NAME WITH THE CITY OF WEST PALM BEACH AND RECEIVE A FL |
| | NUMBER TO BE USED WITH PERMITTING WITHIN THE CITY. |
| | |
| | 2A) THE SUBMITTED FLOOR PLAN DOES NOT PROVIDE THE TYPE |
| | OF FLOORING TO BE INSTALLED, THE TYPE OF UNDERLAYMENT |
| | NOR THE SQUARE FOOTAGE OF THE FLOOR TO BE INSTALLED. |
| | WILL THERE BE ANY BASE, IF SO PLEASE PROVIDE THE TYPE |
| | OF BASE AND LINEAR FOOTAGE. 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | |
| | 2B) THE FLOOR PLAN IS MISSING THE AUTHOR OF THE PLAN. . |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. CERTIFICATION BY CONTRACTOR. 107.3.4.3 |
| | CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION |
| | TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/ |
| | PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES |
| | THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN |
| | THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS |
| | THE SYSTEM UNDER THAT TRADE. |
| | |
| | 3) THE SUBMITTED SALE BROCHURE DOES NOT PROVIDE THE |
| | REQUIRED TEST REPORTS FOR THE SUBMITTED PRODUCT. FLOOR |
| | INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE, VINYL |
| | AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING |
| | COMPLIANCE WITH: |
| | |
| | TYPE I AND II BUILDINGS |
| | 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| | CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| | THE 2017 FBC-B. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |