2021-03-26 16:45:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER SHOWS A 150A TRANSFER SWITCH WITH A 200A
 BREAKER????
  
 2) 200A SERVICE REQUIRES 3/0 CU OR EQUIVALENT AL ENTIRE
 LOAD NOT BEING FED BY ONE MAIN. 310.15(B)(7)(1)
  
 FOR A SERVICE RATED 100 THROUGH 400 AMPERES, THE
 SERVICE CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED
 WITH A ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS
 SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL
 DWELLING UNIT IN A TWO-FAMILY OR MULTIFAMILY DWELLING,
 SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83
 PERCENT OF THE SERVICE RATING. THIS DOES NOT APPLY TO
 YOUR INSTALLATION
  