| Plan Review Notes For Permit 21010451 |
| Permit Number |
21010451 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-26 16:45:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) RISER SHOWS A 150A TRANSFER SWITCH WITH A 200A | | | BREAKER???? | | | | | | 2) 200A SERVICE REQUIRES 3/0 CU OR EQUIVALENT AL ENTIRE | | | LOAD NOT BEING FED BY ONE MAIN. 310.15(B)(7)(1) | | | | | | FOR A SERVICE RATED 100 THROUGH 400 AMPERES, THE | | | SERVICE CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED | | | WITH A ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS | | | SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL | | | DWELLING UNIT IN A TWO-FAMILY OR MULTIFAMILY DWELLING, | | | SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 | | | PERCENT OF THE SERVICE RATING. THIS DOES NOT APPLY TO | | | YOUR INSTALLATION | | | |
|