2021-02-18 09:44:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWING REFERENCES THE FBC SIXTH
 EDITION (2017). THE FBC SEVENTH EDITION (2020) WENT
 INTO EFFECT ON DECEMBER 31, 2020. ALL NEW PERMITS
 APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED TO
 COMPLY WITH AND REFERENCE THE 2020 FBC SEVENTH EDITION.
 FS CHAPTER 553
  
 2) FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
 SPECIFY THIS ON THE SURVEY THAT SHOWS THE GENERATOR
 LOCATION.
  
 3) SEE SIGNATURE REVIEW COMMENTS.
  