| 2021-02-24 13:48:24 | 2ND REVIEW FBC-2020 RES. |
| | PERMIT- 21010426 |
| | 2/24/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS LISTED BELOW FROM |
| | THE 1ST REVIEW STILL EXIST. NOTES HAVE BEEN TO THE |
| | FAILED COMMENTS. |
| | |
| | 1) FAILED. PLEASE UPDATE THE CODE REFERENCES AND PIPE |
| | SIZING TABLES TO THE FBC 7TH EDITION 2020 RESIDENTIAL |
| | AND FBC- 7TH EDITION 2020 FUEL GAS. THE RISER DRAWING |
| | IS INDICATING THE 2029 CODE- PLEASE CORRECT TO INDICATE |
| | 2020. |
| | |
| | 3) FAILED. CORRECT THE SURVEY INDICATING A 5 FT. |
| | CLEARANCE FOR THE GENERATOR EXHAUST TO OPENINGS IN THE |
| | HOUSE. A MINIMUM 10 FT. CLEARANCE IS REQUIRED- SECTION |
| | R303.5.1 FBC RES. MINIMUM 10 FT. CLEARANCE IS REQUIRED- |
| | SECTION R303.5.1 FBC RES. |
| | |
| | 5) FAILED. I WAS UNABLE TO FIND A PERMIT OR GAS PLANS |
| | FOR THE INSTALLATION OF THE BBQ. PLEASE NOTE THAT ANY |
| | GAS PIPING OR GAS-FIRED APPLIANCES PREVIOUSLY |
| | UNPERMITTED OR NOT INSPECTED MUST BE REVIEWED AND |
| | APPROVED AS NEW INSTALLATIONS- SECTION 107.2.1 WPB. THE |
| | BBQ GRILLS AND GAS PIPING SUPPLYING THEM APPEAR TO HAVE |
| | BEEN INSTALLED WITHOUT A PERMIT. BECAUSE YOU ARE |
| | MODIFYING THE SYSTEM, IT IS REQUIRED THAT THE ENTIRE |
| | SYSTEM BE EVALUATED FOR COMPLIANCE. |
| | |
| | REFER TO SECTION G2412.4 (401.4) ADDITIONAL APPLIANCES. |
| | WHERE AN ADDITIONAL APPLIANCE IS TO BE SERVED, THE |
| | EXISTING PIPING SHALL BE CHECKED TO DETERMINE IF IT HAS |
| | ADEQUATE CAPACITY FOR ALL APPLIANCES SERVED. IF |
| | INADEQUATE, THE EXISTING SYSTEM SHALL BE ENLARGED AS |
| | REQUIRED OR SEPARATE PIPING OF ADEQUATE CAPACITY SHALL |
| | BE PROVIDED. |
| | |
| | THE BBQ GRILLS AND PIPING CANNOT BE LABELED AS EXISTING |
| | AND MUST BE REVIEWED AND INSPECTED AS NEW |
| | INSTALLATIONS. PLEASE SHOW THE LOCATIONS OF ALL 3 BBQ |
| | GRILLS ON THE SURVEY DRAWING AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS OR PROVIDE LISTING AND LABEL |
| | INFORMATION. PLEASE NOTE THAT THE GRILLS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH MAN. SPECS. AND HAVE |
| | LOCATION LIMITATIONS- CLEARANCES TO COMBUSTIBLE, |
| | ENCLOSED SPACES, AND OVERHEAD ROOF CONSTRUCTION- |
| | SECTIONS G2408.1 & G2447.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |