| Plan Review Notes For Permit 21010426 |
| Permit Number |
21010426 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-09 15:08:52 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 2ND REVIEW | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) CORRECT THE SURVEY INDICATING A 5 FT. CLEARANCE FOR | | | THE GENERATOR EXHAUST TO OPENINGS IN THE HOUSE. A | | | MINIMUM 10 FT. CLEARANCE IS REQUIRED- SECTION R303.5.1 | | | FBC RES. | | | | | | | | | | | | |
|