| 2021-01-26 10:40:17 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21010426 |
| | 1/26/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE UPDATE THE CODE REFERENCES AND PIPE SIZING |
| | TABLES TO THE FBC 7TH EDITION 2020 RESIDENTIAL AND FBC- |
| | 7TH EDITION 2020 FUEL GAS. |
| | |
| | 2) GAS RISER: THE GENERATOR SPECS INDICATE A FULL LOAD |
| | OF 306,000 BTUH- PLEASE CORRECT. |
| | |
| | 3) CORRECT THE SURVEY INDICATING A 5 FT. CLEARANCE FOR |
| | THE GENERATOR EXHAUST TO OPENINGS IN THE HOUSE. A |
| | MINIMUM 10 FT. CLEARANCE IS REQUIRED- SECTION R303.5.1 |
| | FBC RES. |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICTIONS FOR THE |
| | REGULATORS MARKED UP TO SHOW THE SELECTED MODEL, AND |
| | THE INPUT AND OUTPUT PRESSURES- SECTION G2421 FBC RES. |
| | |
| | 5) I WAS UINABLE TO FIND A PERMIT OR GAS PLANS FOR THE |
| | INSTALLATION OF THE BBQ. PLEAASE NOTE THAT ANY GAS |
| | PIPING OR GAS-FIRED APPLIANCES PREVIOUSLY UNPERMITTED |
| | OR NOT INSPECTED MUST BE REVIWED AND APPROVED AS NEW |
| | INSTALLATIONS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |