| Plan Review Notes For Permit 21010416 |
| Permit Number |
21010416 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-29 14:28:48 | FIRE PROVISO: | | | | | | ALL ACCESS CONTROL SHALL BE INSTALLED PER NFPA 101, CH | | | 7, MEANS OF EGRESS | | | | | | 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED | | | EGRESS | | | DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS | | | SHALL BE | | | PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL | | | LOCKING SYSTEMS | | | RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED | | | THAT ALL OF THE FOLLOWING | | | CONDITIONS ARE MET: | | | (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF | | | THE ELECTRICAL | | | LOCK IS AFFIXED TO THE DOOR LEAF. | | | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION | | | THAT IS READILY | | | OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING | | | CONDITIONS. | | | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE | | | HAND IN THE | | | DIRECTION OF EGRESS. | | | (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE | | | POWER SUPPLY TO | | | THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE | | | DIRECTION | | | OF EGRESS. | | | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE | | | AUTOMATICALLY ELECTRICALLY | | | UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|