| Date |
Text |
| 2021-02-24 17:38:05 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT#21010413 |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | |
| | 1- SHEET C1: PLANS ARE DESIGNED BASED ON THE 2017 FBC. |
| | AS OF DECEMBER 31 OF 2020, THE NEW CODE IN EFFECT IS |
| | THE 2020 FBC, 7TH EDITION. UPDATE DESIGN AND CODE |
| | INFORMATION AS REQUIRED. |
| | CHAPTER 553 FLORIDA STATUTE. |
| | |
| | 2- REVISE WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON |
| | SHEET A1.0 TO REFLECT THE DESIGN PRESSURES OF SEC. |
| | R301.2.1 FBC-RESIDENTIAL, 7TH EDITION (2020). |
| | |
| | 3- SHEET A1.0: ENTRY DOOR SIZE (2'-8") DOESN'T COMPLY |
| | WITH THE THE MIN 32" CLEAR OPENING AS REQUIRED BY SEC. |
| | R311.2 FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | SEC. 605 FBC-EXISTING BUILDING CODE. SEC. 1012.1.1 |
| | FBC-EXISTING BUILDING CODE. |
| | |
| | 4- EAST ELEVATION SHOWN ON SHEET A2.0 DOESN'T MATCH |
| | FLOOR PLAN SHOWN ON SHEET A1.0. REVISE AS REQUIRED TO |
| | MATCH. SEE BATHROOM WINDOW. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | FRAMING OF WALL AT EXISTING BARN DOORS AND NEW WINDOWS |
| | ABOVE AS SHOWN ON PLANS. SPECIFY ALL FRAMING MEMBERS |
| | AND CONNECTORS. |
| | SEC. 605 FBC-EXISTING BUILDING CODE. SEC. 1012.1.1 |
| | FBC-EXISTING BUILDING CODE. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 6- WINDOWS AND DOORS HEAD/JAMB AND SILL DETAILS SHOWN |
| | ON SHEET A2.0 ARE FOR MASONRY CONSTRUCTION. THIS |
| | STRUCTURE IS WOOD FRAMING. REVISE AS REQUIRED. |
| | SEC. 107..1 CITY AMENDMENTS. |
| | |
| | 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)ROOF CLAY TILE AS SPECIFIED ON PLANS. |
| | NOTE: CLEARLY SPECIFY ROOF TILE FASTENING. IF |
| | SPECIFYING ROOF TILE ADHESIVE, THEN PROVIDE PRODUCT |
| | APPROVAL. IF SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE |
| | AND NUMBER OF SCREWS. |
| | |
| | B)ROOF TILE ADHESIVE IF SPECIFIED. SEE ROOF TILE NOA |
| | SUBMITTED FOR LISTED ADHESIVES. AND CLEARLY MARK PADDY |
| | SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING |
| | PERMITS. |
| | |
| | C)AWNING WINDOW NOA 20-0402.07 SUBMITTED. ONLY THE |
| | COVER PAGE WAS SUBMITTED. NEED TO SUBMIT COMPLETE |
| | REPORT INCLUDING THE INSTALLATION INSTRUCTIONS. |
| | |
| | D)EXTERIOR SWINGING DOORS FL20873-R4 AND FL15210-R6. |
| | ONLY THE COVER PAGE WAS SUBMITTED. NEED TO SUBMIT |
| | COMPLETE REPORT INCLUDING THE INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | E)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED: |
| | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| | |
| | 8-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |