| Plan Review Notes For Permit 21010398 |
| Permit Number |
21010398 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-01-20 10:19:41 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THIS PERMIT WAS APPLIED FOR AFTER DECEMBER 31, 2020. | | | IT IS REQUIRED TO COMPLY WITH THE CURRENT CODE WHICH IS | | | THE 2020 FBC. SUBMIT PRODUCT APPROVALS THAT REFERENCE | | | THE 2020 FBC. FBC 107.3.4 | | | | | | 2) ON THE PRODUCT APPROVAL FOR THE FLAT ROOF, PLEASE | | | HI-LIGHT OR CIRCLE THE SYSTEM AND THE MAXIMUM DESIGN | | | PRESSURE FOR IT. IF ENHANCED FASTENING IS REQUIRED FOR | | | THE PERIMETER AND CORNERS, SUBMIT SIGNED AND SEALED RAS | | | 117 CALCULATIONS. FBC 107.2.1 | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|