| 2021-01-20 09:29:28 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SELECTED FASTENING OPTION #3 ON PAGE 51 OF NOA | | | NO. 18-0919.12 HAS A MAXIMUM DESIGN PRESSURE OF -52.5 | | | PSF AND REQUIRES ENHANCED FASTENING TO MEET THE | | | REQUIRED DESIGN PRESSURES FOR THE PROJECT ROOF. GENERAL | | | LIMITATION #7 ALLOWS ENHANCED FASTENING CALCULATIONS IN | | | ACCORDANCE WITH RAS 117. IT ALSO REQUIRES THE | | | CALCULATIONS TO BE SIGNED BY AN ARCHITECT, ENGINEER OR | | | REGISTERED ROOF CONSULTANT. SUBMIT SIGNED AND SEALED | | | CALCULATION. FBC 107.2.1 | | | | | | 2) BECAUSE THE PERMIT FOR THIS PROJECT WAS APPLIED FOR | | | AFTER DECEMBER 31, 2020, IT IS REQUIRED TO COMPLY WITH | | | THE 2020 FBC AND ASCE 7-16. PLEASE MAKE SURE THAT THE | | | RE-SUBMITTAL DOCUMENTS REFERENCE AND COMPLY WITH THE | | | CURRENT CODE (2020 FBC). FBC 107.2.1 |
|