2021-01-20 09:29:28PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SELECTED FASTENING OPTION #3 ON PAGE 51 OF NOA
 NO. 18-0919.12 HAS A MAXIMUM DESIGN PRESSURE OF -52.5
 PSF AND REQUIRES ENHANCED FASTENING TO MEET THE
 REQUIRED DESIGN PRESSURES FOR THE PROJECT ROOF. GENERAL
 LIMITATION #7 ALLOWS ENHANCED FASTENING CALCULATIONS IN
 ACCORDANCE WITH RAS 117. IT ALSO REQUIRES THE
 CALCULATIONS TO BE SIGNED BY AN ARCHITECT, ENGINEER OR
 REGISTERED ROOF CONSULTANT. SUBMIT SIGNED AND SEALED
 CALCULATION. FBC 107.2.1
  
 2) BECAUSE THE PERMIT FOR THIS PROJECT WAS APPLIED FOR
 AFTER DECEMBER 31, 2020, IT IS REQUIRED TO COMPLY WITH
 THE 2020 FBC AND ASCE 7-16. PLEASE MAKE SURE THAT THE
 RE-SUBMITTAL DOCUMENTS REFERENCE AND COMPLY WITH THE
 CURRENT CODE (2020 FBC). FBC 107.2.1