| 2021-02-11 16:29:01 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21010370 |
| | 2/11/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P001 & P111: PLEASE NOTE THAT A SEPARATE |
| | PERMIT IS REQUIRED FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER- SECTION 107.2.1 WPB. A FL. LICENSED PLUMBING |
| | CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| | WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | 2) SHEETS P001, P112, P201: PLEASE IDENTIFY ALL |
| | PLUMBING FIXTURES IN THE EMPLOYEE BREAKROOM AND ADD |
| | PLUMBING PIPING DETAILS WHERE REQUIRED- SECTION 107.2.1 |
| | WPB. THE PLANS INDICATE AN ICE MAKER BOX BUT NO ICE |
| | MAKER APPLIANCE. PLEASE SHOW THE SUPPLY LINE TO THE |
| | APPLIANCE AND PROVIDE A BACKFLOW PREVENTER- SECTION |
| | 608.3 FBC P. |
| | |
| | 3) P002, P112, P201: SHOW THE HOSE BIB WATER LINE |
| | CONNECTION, AND INDICATE THE HOSE BIB WILL BE PROTECTED |
| | BY AN ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM BREAKER |
| | OR A PERMANENTLY ATTACHED HOSE CONNECTION VACUUM |
| | BREAKER- SECTION 608.16.4.2 FBC P. |
| | |
| | 4) P002: PLEASE INCLUDE THE EFFICIENCY RATING OF THE |
| | WATER HEATER INN THE EQUIPMENT SCHEDULE- TABLE C404.2 |
| | FBC EC. |
| | |
| | 5) P202: THE WATER HEATER DETAIL SHOWS THE EXPANSION |
| | TANK LOCATED UPSTREAM OF THE CHECK VALVE WHICH IS |
| | NON-COMPLIANT WITH SECTION 607.3 FBC P. |
| | |
| | 6) P112, P201: INDICATE HOW TEMPERED WATER WILL BE |
| | PROVIDED TO THE LAVATORIES IN COMPLIANCE WITH SECTIONS |
| | 419.5 & 607.1.2 FBC P. |
| | |
| | 7) P002, P112 & P201: PROVIDE AN EQUIPMENT SCHEDULE FOR |
| | THE REMOTE CHILLER AND INDICATE HOW CONDENSATE FROM THE |
| | UNIT WILL BE DISPOSED OF- SECTION 314.2 FBC P. |
| | |
| | 8) A704, A706 DRINKING FOUNTAIN ACCESSIBILITY: REFER TO |
| | SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING |
| | FOUNTAIN INSTALLATION DETAILS AND ELEVATION VIEWS |
| | SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND |
| | SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN. CLEAR |
| | FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO THE |
| | FOUNTAIN- SECTION 602.2 FBC ACC. |
| | |
| | 9) A706: PROVIDE THE BATHROOM LENGTH AND WIDTH |
| | DIMENSIONS AND THE DIMENSIONS OF THE CLEAR FLOOR SPACE |
| | DIAGRAMS FOR THE WATER CLOSETS AND LAVATORIES- SECTIONS |
| | 604.3 & 606.2 FBC ACC. |
| | |
| | 10) A706: THE LOCATION OF THE WATER CLOSET FLUSH |
| | CONTROL IN THE DETAIL IS ON THE WRONG SIDE- SECTION |
| | 604.6 FBC ACC. |
| | |
| | 11) PROVIDE LAVATORY KNEE AND TOE CLEARANCES- SECTION |
| | 606.2 FBC ACC. |
| | |
| | 12) SHOW AREAS OF SLAB DEMOLITION AND PROVIDE A SLAB |
| | REPAIR - SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |