Plan Review Notes
Plan Review Notes For Permit 21010370
Permit Number 21010370
Review Stop P
Sequence Number 1
Notes
Date Text
2021-02-11 16:29:011ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21010370
 2/11/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P001 & P111: PLEASE NOTE THAT A SEPARATE
 PERMIT IS REQUIRED FOR INSTALLATION OF THE BACKFLOW
 PREVENTER- SECTION 107.2.1 WPB. A FL. LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 2) SHEETS P001, P112, P201: PLEASE IDENTIFY ALL
 PLUMBING FIXTURES IN THE EMPLOYEE BREAKROOM AND ADD
 PLUMBING PIPING DETAILS WHERE REQUIRED- SECTION 107.2.1
 WPB. THE PLANS INDICATE AN ICE MAKER BOX BUT NO ICE
 MAKER APPLIANCE. PLEASE SHOW THE SUPPLY LINE TO THE
 APPLIANCE AND PROVIDE A BACKFLOW PREVENTER- SECTION
 608.3 FBC P.
  
 3) P002, P112, P201: SHOW THE HOSE BIB WATER LINE
 CONNECTION, AND INDICATE THE HOSE BIB WILL BE PROTECTED
 BY AN ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM BREAKER
 OR A PERMANENTLY ATTACHED HOSE CONNECTION VACUUM
 BREAKER- SECTION 608.16.4.2 FBC P.
  
 4) P002: PLEASE INCLUDE THE EFFICIENCY RATING OF THE
 WATER HEATER INN THE EQUIPMENT SCHEDULE- TABLE C404.2
 FBC EC.
  
 5) P202: THE WATER HEATER DETAIL SHOWS THE EXPANSION
 TANK LOCATED UPSTREAM OF THE CHECK VALVE WHICH IS
 NON-COMPLIANT WITH SECTION 607.3 FBC P.
  
 6) P112, P201: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES IN COMPLIANCE WITH SECTIONS
 419.5 & 607.1.2 FBC P.
  
 7) P002, P112 & P201: PROVIDE AN EQUIPMENT SCHEDULE FOR
 THE REMOTE CHILLER AND INDICATE HOW CONDENSATE FROM THE
 UNIT WILL BE DISPOSED OF- SECTION 314.2 FBC P.
  
 8) A704, A706 DRINKING FOUNTAIN ACCESSIBILITY: REFER TO
 SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING
 FOUNTAIN INSTALLATION DETAILS AND ELEVATION VIEWS
 SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND
 SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN. CLEAR
 FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO THE
 FOUNTAIN- SECTION 602.2 FBC ACC.
  
 9) A706: PROVIDE THE BATHROOM LENGTH AND WIDTH
 DIMENSIONS AND THE DIMENSIONS OF THE CLEAR FLOOR SPACE
 DIAGRAMS FOR THE WATER CLOSETS AND LAVATORIES- SECTIONS
 604.3 & 606.2 FBC ACC.
  
 10) A706: THE LOCATION OF THE WATER CLOSET FLUSH
 CONTROL IN THE DETAIL IS ON THE WRONG SIDE- SECTION
 604.6 FBC ACC.
  
 11) PROVIDE LAVATORY KNEE AND TOE CLEARANCES- SECTION
 606.2 FBC ACC.
  
 12) SHOW AREAS OF SLAB DEMOLITION AND PROVIDE A SLAB
 REPAIR - SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  