| 2021-01-27 10:51:16 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21010370 |
| | ADD: 700 S. ROSEMARY AVE. SUITE: 106 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ??? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JAN. 28/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET DECLARED DEFERRED SUBMITTALS: |
| | |
| | 1A) RACK STORAGE SYSTEMS OVER 5 FEET 9 INCHES HIGH |
| | REQUIRE A SEPARATE PERMIT WITH REVIEW AND ASSOCIATED |
| | FEES. 2017 |
| | W. P. B. ADMINISTRATIVE CODE SECTION 105.2 BUILDING 6. |
| | |
| | 1B) SIGN PERMITS REQUIRE A SEPARATE PERMIT WITH REVIEW |
| | AND ASSOCIATED FEES SHEETS A-501, A-502 & A-503). 2017 |
| | W. P. B. ADMINISTRATIVE CODE SECTION 105.1 |
| | |
| | 2) PLEASE NOTE SHEETS A-201 & A-202 EXTERIOR ELEVATIONS |
| | NOT TO BE REVIEWED UNDER THIS PERMIT. THERE IS AN |
| | APPLIED PERMIT 21010228 FOR THE EXTERIOR ELEVATIONS. |
| | NOT PART OF THIS PERMIT. |
| | |
| | 3)) SHEET A-008 1ST FLOOR EGRESS PLAN: |
| | 3A) SURROUNDING THE TENANT SPACE THE WALL TYPE |
| | DESIGNATION IS NOT REPRESENTED AS RATED OR NOT. THE |
| | WALL SYMBOL USED DESIGNATES EXIT TRAVEL LESS THAN 250 |
| | FEET IN SPRINKLERED BUILDINGS. PLEASE CORRECT. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3B) PLEASE NOTE CITY PLACE WAS DEVELOPED AS A MALL |
| | CONCEPT WITH THE REAR EXIT FROM THE TENANT SPACE |
| | OPENING INTO A EXIT PASSAGEWAY. WHERE EXIT PASSAGEWAYS |
| | PROVIDES A SECONDARY MEANS OF EGRESS FROM A TENANT |
| | SPACE, THE EXIT PASSAGE WAY SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH 1024. EXIT PASSAGEWAYS ARE SEPARATED BY |
| | NOT LESS THAN 1-HOUR FIRE BARRIERS IN ACCORDANCE WITH |
| | 707 AND FIRE PROTECTION OF OPENINGS IN FIRE BARRIERS |
| | SHALL NOT BE LESS THAN 1 HOUR SEE 2020 FBC-B TABLE |
| | 716.5. |
| | |
| | 3C) THE REAR EXIT DOOR LABELED 152 AND REAR EXIT DOORS |
| | FROM THE STORAGE ROOM ALSO LABELED DOOR 152 DOES NOT |
| | SHOW ON THE DOOR SCHEDULE SHEET A-006. FIRE PROTECTION |
| | OF OPENINGS IN FIRE BARRIERS SHALL NOT BE LESS THAN 1 |
| | HOUR SEE 2020 FBC-B TABLE 716.5. |
| | |
| | 3D) PLEASE NOTE THE DOOR SCHEDULE SHOWS DOORS 101, 102, |
| | & 103 BUT THEY ARE NOT IDENTIFIED ON THE EGRESS FLOOR |
| | PLAN. ALL DOORS WITHIN THE EXIT PASSAGEWAY SHOULD BE |
| | 1-HOUR FIRE RATED NOT 45 MIN. FIRE PROTECTION OF |
| | OPENINGS IN FIRE BARRIERS SHALL NOT BE LESS THAN 1 HOUR |
| | SEE 2020 FBC-B TABLE 716.5. |
| | |
| | 4) SHEET A-009 2ND FLOOR EGRESS PLAN REMOTE STORAGE: |
| | 4A) BOTH SHEETS A-009 AND A-110 BOTH SHOW THE EXIT |
| | PASSAGEWAY AS A ONE-HOUR FIRE RATED EXIT PASSAGEWAY. |
| | THE DOUBLE DOORS LEADING INTO THE STORAGE UNIT ARE NOT |
| | IDENTIFIED WITH AN IDENTIFICATION TAG. THE DOOR |
| | SCHEDULE ON SHEET A-006 DOES IDENTIFY THE REMOTE |
| | STORAGE LOADING DOORS AS 111 AND AS 90-MINUTE DOORS? |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4B) FIRE PROTECTION OF OPENINGS IN FIRE BARRIERS SHALL |
| | NOT BE LESS THAN 1 HOUR SEE 2020 FBC-B TABLE 716.5. THE |
| | EXCEPTION IS IF THIS IS AN EXTENSION OF A VERTICAL EXIT |
| | 4 STORIES OF MORE, THEN THE 90 MINUTE FIRE RATING WOULD |
| | BE REQUIRED SINCE IT IS THE EXTENSION OF A VERTICAL |
| | EXIT, THEN ALL DOORS LEADING INTO THE EXIT PASSAGEWAY |
| | WOULD REQUIRE 90 MINUTE DOORS. |
| | |
| | 4C) SHEET F-220 PATH OF GOODS. SHOWS 2 PROPOSED PICK-UP |
| | PARKING SPACES, WHERE ARE THESE PARKING SPACES LOCATED, |
| | IT WOULD WITH RESPECT TO THE OVERALL LAYOUT OF CITY |
| | PLACE BE IN THE PARKING GARAGE? IF SO SEE ZONING |
| | COMMENT. 107.2.1.2. |
| | IT APPEARS THE EXTERIOR DOORS ARE MISSING FROM THE END |
| | OF THE EXIT PASSAGEWAY. |
| | |
| | 5) SHEET A-701 DOES SHOW IN THE FRONT CASH WRAP A |
| | SECTION OF THE CASH WRAP AS ACCESSIBLE AT A HEIGHT OF |
| | 34 INCHES. THE REMAINDER OF THE FRONT CASH-WRAP AND |
| | BACK CASH-WRAP AT A HEIGHT OF 42 INCHES. PLEASE SHOW |
| | COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE SECTION |
| | 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28 |
| | INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |