| Plan Review Notes For Permit 21010362 |
| Permit Number |
21010362 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-07-19 09:26:55 | WINDOWS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWING PROVIDED FROM RYAN HOWARD P.E. SHOWS THE | | | WRONG CODE VERSION (2017 FBC) SHOULD BE 2020 FBC. | | | 2) THE PRODUCT APPROVAL PROVIDED FOR THE FIXED WINDOWS | | | REQUIRES SHUTTERS - PLEASE PROVIDE THE SHUTTER PRODUCT | | | APPROVALS OR THE PERMIT NUMBER FOR THE EXISTING | | | SHUTTERS. DRAWINGS PROVIDED SHOWS FIXED WINDOW TO BE | | | IMPACT RATED. | | | 3) PLEASE PROVIDE THE COMPLETE PRODUCT APPROVAL FOR THE | | | MULL BARS. | | | |
|