Plan Review Notes
Plan Review Notes For Permit 21010356
Permit Number 21010356
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-01-25 12:32:05FIRE LINE LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA
 24 AND SHALL BE COORDINATED WITH THE OFFICE OF FIRE
 MARSHAL, THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE
 PLANNER, AND THE CITY'S PLANNING AND ZONING OFFICE.
  
 FIRE LINE (UNDERGROUND) MUST BE SUBMITTED UNDER A
 SEPERATE PERMIT PER NFPA 24
  
 FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT MORE
 THAN 100 FT (30.5 M) FROM THE NEAREST FIRE HYDRANT
 CONNECTED TO AN APPROVED WATER SUPPLY
  
 FOR THE PROPOSED FIRE PUMP THE PRIMARY AND SECONDARY
 POWER SOURCES MUST BE SPECIFIED.
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 DURING ON SITE FIRE INSPECTIONS. FAILURE TO FOLLOW
 THESE PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.