| 2021-01-25 12:32:05 | FIRE LINE LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA | | | 24 AND SHALL BE COORDINATED WITH THE OFFICE OF FIRE | | | MARSHAL, THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE | | | PLANNER, AND THE CITY'S PLANNING AND ZONING OFFICE. | | | | | | FIRE LINE (UNDERGROUND) MUST BE SUBMITTED UNDER A | | | SEPERATE PERMIT PER NFPA 24 | | | | | | FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT MORE | | | THAN 100 FT (30.5 M) FROM THE NEAREST FIRE HYDRANT | | | CONNECTED TO AN APPROVED WATER SUPPLY | | | | | | FOR THE PROPOSED FIRE PUMP THE PRIMARY AND SECONDARY | | | POWER SOURCES MUST BE SPECIFIED. | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | DURING ON SITE FIRE INSPECTIONS. FAILURE TO FOLLOW | | | THESE PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | | | | |
|