Plan Review Notes
Plan Review Notes For Permit 21010330
Permit Number 21010330
Review Stop G
Sequence Number 1
Notes
Date Text
2021-02-08 09:02:061ST REVIEW FBC-2020 RES.
 PERMIT- 21010330
 2/8/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THE FOLLOWING ITEMS ABOUT THE
 APPLICATION:
  
 A) THE APPLICATION HAS A CHECK MARK IN THE SUB-PERMIT
 BOX. THIS IS A PRIMARY GAS PERMIT AND NOT A SUB-PERMIT
 OF THE MASTER PERMIT- 20070012.
  
 B) A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR
 INSTALLATION OF THE NEW GENERATOR- SECTION 105.1 &
 107.2.1 WPB.
  
 C) THE $500.00 VALUE ON THE APPLICATION DOES NOT APPEAR
 TO INCLUDE THE COSTS OF THE NEW APPLIANCES- RANGE,
 DRYER AND BBQ GRILL. PERMIT VALUE IS BASED ON THE COSTS
 ASSOCIATED WITH LABOR, MATERIALS, APPLIANCES,
 EQUIPMENT, FIXTURES, SITE WORK AND DESIGN FEES- SECTION
 107.2.1 WPB. PLEASE PROVIDE A COPY OF THE SIGNED
 CONTRACT AND/OR COPIES OF ESTIMATES AND INVOICES.
  
 2) FOR THE PURPOSE OF GAS PIPING REVIEW, PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATION SHEETS FOR THE RANGE,
 DRYER, BBQ, AND THE GENERATOR THAT SPECIFICALLY SHOW
 THE BTUH LOADS AND INPUT PRESSURES. COMPLETE SPECS AND
 INSTALLATION MANUALS ARE REQUIRED TO BE ONSITE AT TIME
 OF INSPECTION- SECTION 107.2.1 WPB.
  
 3) SHEET G-1: PLEASE UPDATE THE FBC- 2017 CODE
 REFERENCES. THE FBC- 2020 7TH EDITION CODES WENT INTO
 EFFECT 12/31/2020.
  
 4) G-1: SHOW THE CLEARANCE DISTANCE FROM THE BBQ GRILL
 TO OPERABLE OPENINGS AND AIR INTAKES IN THE BUILDING-
 SECTIONS M1801.1, G2427.3.2, G2427.8 & G2447.1 FBC RES.
  
 5) G-1 GAS RISER: SHOW REGULATORS AT THE GENERATOR,
 DRYER, AND RANGE WHICH WILL ALL BE OPERATING AT
 PRESSURES LOWER THAN 11 IN. WC.- SECTION 2421 FBC RES.
 SHOW A FLEX CONNECTOR AT THE GENERATOR AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS.
  
 6) G-1: PLEASE NOTE THAT THE GENERATOR EXHAUST OUTLET
 SHALL BE LOCATED A MINIMUM OF 10 FT. FROM MECHANICAL
 AIR INTAKES AND OPERABLE OPENINGS IN THE BUILDING-
 SECTION R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  