| Plan Review Notes For Permit 21010326 |
| Permit Number |
21010326 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-01 09:05:44 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE | | | THE DRAWINGS TO SHOW THE DESIGN CRITERIA BASED ON THE | | | CODE IN EFFECT (2020 FBC AND ASCE 7-16) | | | 2) PLEASE SHOW THE SMOKE ALARM LOCATIONS THROUGH OUT | | | THE EXISTING HOUSE TO COMPLY WITH FBC R314.2.2 | | | ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | 3) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG | | | WINDOWS (02-1120.03) HAS EXPIRED - PLEASE PROVIDE AN | | | UPDATED VERSION. | | | 4) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE | | | ROOFING SYSTEM. | | | 5) ALL PRODUCT APPROVALS AND SHOP DRAWINGS NEED TO BE | | | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER | | | OF RECORD. | | | 6) THE DESIGN CRITERIA FOR THE TRUSS DRAWINGS SHOWN ON | | | THE TRUSS ENGINEERING NEEDS TO BE REVISED TO REFLECT | | | THE CODE IN EFFECT (2021 FBC AND ASCE 7-16) | | | | | | | | | |
|