| Notes |
| Date |
Text |
| 2021-01-28 07:40:22 | 1ST REVIEW FBC-2020 RES. | | | PERMIT- 21010298 | | | 1/28/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A GAS SUB-PERMIT APPLICATION FOR HOOKUP OF | | | THE GAS TO THE NEW GENERATOR- SECTION 105.1 WPB. | | | | | | 2) THE GENERATOR INSTALLED UNDER PERMITS 06031477 & | | | 06050871 WAS A 40 KW, THE NEW GENERATOR IS A 30 KW. | | | CLARIFY WHAT CHANGES, IF ANY, WILL BE MADE TO THE GAS | | | PIPING SYSTEM TO ACCOMMODATE THE NEW GENERATOR- PROVIDE | | | A GAS RISER DRAWING SHOWING THE GAS SUPPLY LINE, | | | REGULATOR AND FLEX CONNECTOR TO THE NEW GENERATOR- | | | SECTIONS 107.1 & 107.3.5.3 WPB. PLEASE SUBMIT SPECS FOR | | | ALL NEW COMPONENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|