Plan Review Notes
Plan Review Notes For Permit 21010266
Permit Number 21010266
Review Stop B
Sequence Number 4
Notes
Date Text
2021-03-11 10:35:4303/11/21 COURTESY REVIEW OF PLANS EMAILED BY JON OLSON:
 COMMENTS:
 1- TYPE OF OCCUPANCY ONLY LISTS THE PRIMARY OCCUPANCY
 F1. IT DOESN'T SPECIFY THE OTHER OCCUPANCY, MERCANTILE.
 2- INFORMATION UNDER THE OCCUPANCY LOAD HEADING: PLEASE
 SPECIFY THE FACTORY F-1 OCCUPANT LOAD AND INCLUDE EACH
 WORKROOM AREA AS SHOWN ON THE FLOOR PLAN.
 AND, REMOVE THE BUSINESS, OFFICE AREAS AND
 STORAGE/MECHANICAL OCCUPANCY LOAD CALCULATIONS TO AVOID
 CONFLICTS. THESE OCCUPANCIES ARE NOT PART OF THIS
 PROJECT.
 3- PLEASE MAKE SURE INFORMATION IS REVISED IN ALL OTHER
 PLANS, INCLUDING THE COVER PAGE TO AVOID CONFLICTS.
  
  
  
  
  
 *****PREVIOUS COMMENTS:
  
 REVISION THIRD SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 REVISION #21010266
  
  
 1- SHEET A1.0:
  
 ORIGINAL COMMENT:
 A) SHEET A1.0 SHOWS REVISED LAYOUT SHOWING NEW ROOMS.
 THE NEW ROOMS ARE NO IDENTIFIED ON THE FLOOR PLAN.
 PLEASE IDENTIFY THE ROOMS AND THEIR USE. SEC. 102.2 AND
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 (NOTE: COORDINATE WITH COMMENT #2 BELOW)
  
 INFORMATION SHOWN ON SHEET A1.0 AND LS1-0 IS OK FOR
 BUILDING REVIEW. "WORKROOM/ART STUDIO" CLASSIFIES AS
 F-1 OCCUPANCY FOR ENTIRE BUILDING. THIS IS OK UNDER THE
 BUILDING REVIEW, BUT IT LOOKS LIKE THERE IS AN ISSUE
 WITH ZONING REGARDING THE PROPOSED USE F-1. TO AVOID
 CONFLICTS/DELAYS BUILDING REVIEW WILL BE APPROVED ONCE
 ZONING ISSUES ARE ADDRESSED AND PLANS ARE REVISED
 ACCORDINGLY. COORDINATE WITH LINDA LOUIE (SENIOR
 PLANNER)
 BASED ON PHONE CONVERSATION WITH LINDA LOUIE (SENIOR
 PLANER), IT LOOKS LIKE ZONING IS EXPECTING TO HAVE SOME
 SORT OF "RETAIL STORE" IN ORDER TO APPROVE THE PLANS.
 PLEASE COORDINATE WITH LINDA LOUIE.
  
 NOTE:
 YOU CAN HAVE RETAIL SPACE IN THIS BUILDING. THIS WILL
 CREATE A MIXED USE OF WORKROOM/ART STUDIO (F-1
 OCCUPANCY) AND RETAIL AREA (MERCANTILE OCCUPANCY). KEEP
 THIS IN CONSIDERATION WHEN REVISING PLANS. REVISE CODE
 REFERENCES INFORMATION ON LIFE SAFETY PLAN LS1.0. KEEP
 IN MIND THAT NUMBER OF PEOPLE CHANGES FOR MERCANTILE
 OCCUPANCIES (TABLE 1004.1.2 FBC-BUILDING).
 ALSO, REVISE ALL PLANS ACCORDINGLY REFLECTING ALL THE
 CHANGES TO AVOID CONFLICTS/DELAYS. AND, CODE DATA
 INFORMATION ON THE COVER SHEET NEEDS TO BE REVISED ALSO
 TO MATCH ALL REVISIONS.
  
  
 2- SEE ITEM #1 ABOVE.
  
 3- REVISED PLANS NEED TO BE REVIEWED BY PALM BEACH
 COUNTY FOR IMPACT FEE ASSESSMENT.
  
 NOTE: THIS WILL DONE AFTER THIS REVISION IS APPROVED BY
 ALL TRADES.
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 4- OK.
 5-OK.
  
 6- NEW COMMENT:
 A NEW CERTIFICATE OF OCCUPANCY IS REQUIRED. THIS IS A
 CHANGE OF OCCUPANCY FROM WAREHOUSE. SEC. 506
 FBC-EXISTING BUILDING AND SEC. 1001.3 FBC-EXISTING
 BUILDING.
  
  
 NOTE:
 ALL ARCHITECTURAL PLANS UPLOADED TO PROJECTDOX HAVE A
 COPY OF THE ARCHITECT'S SEAL AND SIGNATURE. NEED TO
 HAVE ARCHITECT'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTES.
  
 THERE ARE TWO WAYS TO PROVIDE ARCHITECT'S ORIGINAL
 SEAL/SIGNATURE:
 1) UPLOAD PLANS TO PROJECTDOX WITH ARCHITECT'S DIGITAL
 SIGNATURE
 OR
 2) BRING HARDCOPIES OF ALL ARCHITECTURAL PLANS TO CITY
 HALL WITH ARCHITECT'S ORIGINAL SEAL AND SIGNATURE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]