2021-02-18 18:31:03REVISION SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 REVISION #21010266
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- SHEET A1.0:
  
 A) SHEET A1.0 SHOWS REVISED LAYOUT SHOWING NEW ROOMS.
 THE NEW ROOMS ARE NO IDENTIFIED ON THE FLOOR PLAN.
 PLEASE IDENTIFY THE ROOMS AND THEIR USE. SEC. 102.2 AND
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 (NOTE: COORDINATE WITH COMMENT #2 BELOW)
 USE OF SPACE IS NOT CLEAR. THE CODE REFERENCE
 INFORMATION ON THE LIFESAFETY PLAN ON SHEET LS1.0
 SPECIFIES BUSINESS/ART MERCHANDISE STUDIO AS THE
 PRIMARY OCCUPANCY. THIS LOOKS LIKE THERE ARE TWO
 DIFFERENT OCCUPANCIES. BUSINESS AND ART MERCHANDISE
 STUDIO. THE ART MERCHANDISE STUDIO CAN BE EITHER
 ASSEMBLY A-3 (ART GALLERY) OR FACTORY BASED ON THE
 SCOPE OF WORK DONE ON THE WORKROOMS SHOWN ON THE FLOOR
 PLAN.
 ALSO, PROPOSED FLOOR PLAN ONLY SHOWS OFFICE. IT DOESN'T
 SHOW ART MERCHANDISE STUDIO. REVISE PLANS AS REQUIRED
 AND COORDINATE WITH COMMENT #2 BELOW).
  
 ORIGINAL COMMENT:
 B)SPECIFY SIZE AND HARDWARE OF NEW DOORS LEADING TO THE
 NEW ROOMS TO VERIFY ACCESSIBILITY. SEC. 801.3
 FBC-EXISTING BUILDING AND SEC. 202.4 FBC-ACCESSIBILITY.
  
 RESPONSE:
 BASED ON REVISED DOOR SCHEDULE ON SHEET A3.0 DOORS #104
 AND #105 DON'T COMPLY. DOOR #104 DOESN'T HAVE THE MIN.
 CLEAR WIDTH REQUIRED BY SEC. 404.2.3 FBC-ACCESSIBILITY.
 AND, DOUBLE DOOR #105 NEEDS TO HAVE AT LEAST ONE LEAF
 THAT COMPLIES WITH SEC. 404.2.2 FBC-ACCESSIBILITY.
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 2- LIFE SAFETY PLAN SHEET LS1.0 DESCRIBES TYPE OF
 OCCUPANCY TO BE BUSINESS AS THE PRIMARY OCCUPANCY AND
 STORAGE S-2 AS THE ACCESSORY OCCUPANCY. ACCESSORY
 OCCUPANCY CAN NOT BE MORE THAN 10 PERCENT OF THE FLOOR
 AREA. THEREFORE, THESE ARE TWO SEPARATE OCCUPANCIES.
 REVISE AS REQUIRED.
  
 RESPONSE:
 USE OF SPACE IS NOT CLEAR. THE CODE REFERENCE
 INFORMATION SPECIFIES BUSINESS/ART MERCHANDISE STUDIO
 AS THE PRIMARY OCCUPANCY. THIS LOOKS LIKE THERE ARE TWO
 DIFFERENT OCCUPANCIES. BUSINESS AND ART MERCHANDISE
 STUDIO. THE ART MERCHANDISE STUDIO CAN BE EITHER
 ASSEMBLY A-3 (ART GALLERY) OR FACTORY BASED ON THE
 SCOPE OF WORK DONE ON THE WORKROOMS.
 ALSO, PROPOSED FLOOR PLAN ONLY SHOWS OFFICE. IT DOESN'T
 SHOW ART MERCHANDISE STUDIO.
  
 IN ADDITION, THE CODE REFERENCE INFORMATION ALSO
 SPECIFIES STORAGE AS THE ACCESSORY OCCUPANCY. FLOOR
 PLAN DOESN'T SHOW ANY STORAGE. IT ONLY SHOWS TWO
 WORKROOMS.
  
 ALSO, AN ACCESSORY OCCUPANCY CAN NOT BE MORE THAN 10
 PERCENT OF THE FLOOR AREA. THEREFORE, THESE ARE TWO
 SEPARATE OCCUPANCIES. (REPEAT COMMENT).
  
 REVISE AS REQUIRED. COORDINATE WITH ITEM #1 ABOVE.
  
  
 3- REVISED PLANS NEED TO BE REVIEWED BY PALM BEACH
 COUNTY FOR IMPACT FEE ASSESSMENT.
  
 NOTE: THIS WILL DONE AFTER THIS REVISION IS APPROVED BY
 ALL TRADES.
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 4- OK.
  
 5-REVISED ENERGY CALCULATIONS FORM SUBMITTED:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B)ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND LICENSE
 NUMBER) ON ENERGY FORM AS REQUIRED BY SEC. C103.1.1.1.2
 FBC-ENERGY CONSERVATION.
  
 6- NEW COMMENT:
 A NEW CERTIFICATE OF OCCUPANCY IS REQUIRED. THIS IS A
 CHANGE OF OCCUPANCY FROM WAREHOUSE. SEC. 506
 FBC-EXISTING BUILDING AND SEC. 1001.3 FBC-EXISTING
 BUILDING
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,