2021-01-19 15:28:18REVISION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 REVISION #21010266
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- SHEET A1.0:
 A) SHEET A1.0 SHOWS REVISED LAYOUT SHOWING NEW ROOMS.
 THE NEW ROOMS ARE NO IDENTIFIED ON THE FLOOR PLAN.
 PLEASE IDENTIFY THE ROOMS AND THEIR USE. SEC. 102.2 AND
 SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE:
 ELECTRICAL PLAN SHEET E1.1 IDENTIFIES THESE ROOMS AS
 STORAGE, WHILE THE LIFE SAFETY PLAN SHEET LS1.0
 IDENTIFIES THESE ROOMS AS "ROOM". PLEASE COORDINATE
 NAME OF ROOMS ON ALL FLOOR PLANS FOR PROPER PLAN REVIEW
 PROCESS AND TO AVOID CONFLICTS.
  
 B) SPECIFY SIZE AND HARDWARE OF NEW DOORS LEADING TO
 THE NEW ROOMS TO VERIFY ACCESSIBILITY. SEC. 801.3
 FBC-EXISTING BUILDING AND SEC. 202.4 FBC-ACCESSIBILITY.
  
 2- LIFE SAFETY PLAN SHEET LS1.0 DESCRIBES TYPE OF
 OCCUPANCY TO BE BUSINESS AS THE PRIMARY OCCUPANCY AND
 STORAGE S-2 AS THE ACCESSORY OCCUPANCY. ACCESSORY
 OCCUPANCY CAN NOT BE MORE THAN 10 PERCENT OF THE FLOOR
 AREA. THEREFORE, THESE ARE TWO SEPARATE OCCUPANCIES.
 REVISE AS REQUIRED.
  
 3- REVISED PLANS NEED TO BE REVIEWED BY PALM BEACH
 COUNTY FOR IMPACT FEE ASSESSMENT.
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 4- PLANS WERE REVISED SHOWING NEW PARTITIONS. NEED TO
 SPECIFY THE VALUE FO THE ADDITIONAL SCOPE OF WORK. SEC.
 109.3 CITY AMENDMENTS.
  
 5-PROVISO ITEMS NOT ADDRESSED:
 A)ENERGY CALCULATIONS WERE NOT REVISED. SEE COPY OF
 PROVISO BELOW.
 NOTE: IN ADDITION ENERGY CALCULATIONS NEED TO BE
 REVISED REFLECTING THE OWNER CHANGES.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSPECTIONS):
 1- REVISE ENERGY CALCULATIONS: WINDOWS AND DOORS
 INFORMATION DON'T MATCH PLANS. SEE PLANS AND REVISE AS
 REQUIRED.
 2- OK
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]