| 2021-04-15 10:49:59 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) 2ND FLOOR ELECTRICAL PLAN SHOWS ONLY CARBON MONOXIDE |
| | DETECTORS OUTSIDE THE BEDROOMS - A COMBINATION SMOKE |
| | AND CARBON MONOXIDE DETECTOR CAN BE SHOWN - R314.7.4 |
| | 2) SHEET 1 WAS NOT REVISED AS NOTED ON THE COMMENT |
| | DRAWING. PLEASE SHOW A BATH/TOILET ROOM DOOR WIDTH OF A |
| | CLEAR OPENING OF 29 INCHES ON THE FIRST FLOOR TO COMPLY |
| | WITH FBC R320.1.1 - FBC ACCESSIBILITY 404.2.3 CLEAR |
| | WIDTH. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS |
| | SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE |
| | STOP, WITH THE DOOR OPEN 90 DEGREES. |
| | 3) SHEET 1 WAS NOT REVISED AS NOTED ON THE COMMENT |
| | DRAWING. PLEASE SHOW THE GARAGE CEILING FIRE PROTECTION |
| | FROM HABITABLE ROOMS ABOVE THE GARAGE PER FBC R302.6 |
| | (5/8 TYPE X DRYWALL). |
| | 4) SHEET 1 WAS NOT REVISED AS NOTED ON THE COMMENT |
| | DRAWING. PLEASE SHOW THE REQUIRED DRYWALL UNDER THE |
| | ENCLOSED STAIR TO COMPLY WITH FBC R302.7 UNDER-STAIR |
| | PROTECTION. |
| | ENCLOSED SPACE UNDER STAIRS THAT IS ACCESSED BY A DOOR |
| | OR ACCESS PANEL SHALL HAVE WALLS, UNDER-STAIR SURFACE |
| | AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH |
| | 1/2-INCH (12.7 MM) GYPSUM BOARD. |
| | 5) WINDOW AND DOOR PRODUCT APPROVALS WILL BE DEFERRED |
| | AS PER NOTE ON THE DRAWINGS COVER PAGE. |
| | 6) PRODUCT APPROVAL PROVIDED FOR THE METAL ROOFING |
| | SYSTEM (-82.5) DOES NOT MEET THE REQUIRED WIND DESIGN |
| | PRESSURES FOR ROOF WIND ZONES 2R PER DRAWING MARKED |
| | COVER PAGE (-102.7) |
| | 7) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| | ENGINEER. |
| | 8) NEED THE ORIGINAL SIGNED AND SEALED SOIL REPORT. |
| | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. IF YOUR |
| | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR |
| | DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE |
| | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE |
| | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL |
| | 9) DRAWINGS SHOW THE ROOFING AND WINDOW AND DOOR |
| | PRODUCT APPROVALS ARE TO BE DEFERRED - YET NEW PRODUCT |
| | APPROVALS HAVE BEEN SUBMITTED FOR THE ROOFING. IS THE |
| | ROOFING TO BE DEFERRED? ROOFING SYSTEM AND WINDOW AND |
| | DOOR PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY |
| | LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION |
| | DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |