| 2021-04-14 13:38:25 | POOL HOUSE ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PRODUCT APPROVALS PROVIDED FOR THE WINDOWS AND DOORS | | | NEED TO BE COMPLETE - FRONT PAGES WERE PROVIDED - THE | | | INSTALLATION DRAWINGS ARE MISSING - PLEASE PROVIDE THE | | | INSTALLATION DRAWINGS FOR EACH DOOR AND WINDOW PRODUCT | | | APPROVAL. PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA | | | STATE PRODUCT APPROVALS FOR THE WINDOWS, DOORS. | | | 2) PRODUCT APPROVAL FOR THE FLAT DECK (LOW SLOPE) | | | ROOFING = THERE ARE MULTIPLE "SYSTEM TYPES"IN THE | | | ROOFING PRODUCT APPROVAL. PLEASE CHOOSE A ROOFING | | | "SYSTEM TYPE" IN THE PRODUCT APPROVAL THAT SHOWS THE | | | REQUIRED WIND DESIGN PRESSURE - PLEASE CIRCLE THE | | | ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL - IF | | | NEEDED PLEASE PROVIDE ADDITIONAL ATTACHMENT DETAILS | | | FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND | | | 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE THEN THE | | | CHOSEN ROOFING SYSTEM - SEE NOTES ON THE PRODUCT | | | APPROVAL. (NOTE 7 OR 9). |
|