Plan Review Notes
Plan Review Notes For Permit 21010170
Permit Number 21010170
Review Stop P
Sequence Number 1
Notes
Date Text
2021-01-25 13:51:031ST REVIEW FBC-2020 RES.
 PERMIT- 21010170
 1/25/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $28,000 JOB VALUE ON THE APPLICATION IS VERY LOW
 FOR THE SCOPE OF WORK FOR THE PROJECT AS SHOWN ON THE
 PLANS. PLEASE PROVIDE AN ACCURATE JOB VALUE THAT
 INCLUDES THE TOTAL COST OF LABOR, MATERIALS, EQUIPMENT,
 APPLIANCES, FIXTURES, SITE WORK, DESIGN FEES FOR ALL
 PHASES OF CONSTRUCTION INCLUDING BUILDING, MECHANICAL,
 ELECTRICAL, AND PLUMBING- SECTION 109.3 WPB. SUBMIT
 DOCUMENTATION INCLUDING COPIES OF SIGNED CONTRACTS
 AND/OR ESTIMATES, INVOICES ETC.
  
 2) PROVIDE SUB-PERMIT APPLICATIONS FOR PLUMBING AND
 GAS- SECTION 105.1 WPB.
  
 3) SHEET A-2: SHOW THE AREAS OF SLAB DEMOLITION FOR
 PLUMBING PIPING INSTALLATION, AND PROVIDE AN ENGINEERED
 SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 4) A-3: PLEASE PROVIDE THE WIDTH MEASUREMENT OF THE
 TOILET ROOM BY BEDROOM #2- SECTION R307 FBC RES.
  
 5) P-2: PLEASE UPDATE THE FBC- 17 REFERENCE TO THE FBC
 7TH EDITION- 2020.
  
 6) P-2: PROVIDE THE EFFICIENCY RATING OF THE NEW GUEST
 HOUSE WATER HEATER- TABLE C404.2 FBC EC.
  
 7) P-2: PLEASE PROVIDE A PLAN NOTE AT THE NEW WATER
 HEATER REFERENCING THE INSTALLATION DETAIL ON P-4-
 SECTION 107.2.1 WPB.
  
 8) P-2: PROVIDE A DEDICATED SHUT OFF VALVE FOR THE COLD
 WATER INLET TO THE EXISTING WATER HEATER- SECTION
 P2903.9.2 FBC RES.
  
 9) P-2: BASED ON THE PLAN IT APPEARS THAT THE POOL
 HOUSE IS BEING CONVERTED TO A SECOND DWELLING UNIT ON
 THE PROPERTY WHICH MAY REQUIRE THE INSTALLATION OF A
 BACKFLOW PREVENTER ASSEMBLY AT THE POINT OF DELIVERY IN
 ACCORDANCE WITH THE CITY OF WEST PALM CROSS UTILITIES
 DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM. PLEASE
 CONTACT THE UTILITIES DEPARTMENT FOR FURTHER
 INFORMATION- 561-822-2240.THE TYPE OF BACKFLOW ASSEMBLY
 REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD
 POSED BY THE WATER USER.
  
 10) P-4: PLEASE UPDATE THE FBC- 17 REFERENCES AND
 SECTION NUMBERS TO THE FBC RESIDENTIAL 7TH EDITION-
 2020.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  