| 2021-01-25 15:32:10 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 21010170 |
| | 1/25/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-1: PLEASE UPDATE THE FBC- 2017 AND CODE |
| | SECTION REFERENCES TO THE FBC- RESIDENTIAL 7TH EDITION |
| | 2020. |
| | |
| | 2) P-1 GAS RISER: SHOW THE REQUIRED REGULATORS AT THE |
| | COOKTOP AND THE DRYER AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS- SECTION G2421.1 & G2421.2 FBC RES. |
| | |
| | 3) P-1: REVISE THE FLOOR PLAN AND RISER TO SHOW THE |
| | EXISTING LINE FROM THE METER TO THE EXISTING TANKLESS |
| | GAS WATER HEATER- G2412.3 & G2412.4 FBC RES. |
| | |
| | 4) P-1: SUBMIT MANUFACTURER'S SPECIFICATIONS SHOWING |
| | THE BTUH CAPACITIES AND INPUT PRESSURES OF THE NEW |
| | GAS-FIRED APPLIANCES- SECTION G2408.1 FBC RES. |
| | |
| | 5) P-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | COOKTOP AND MAKEUP AIR FOR THE DRYER- SECTION G2407.1 |
| | FBC RES. |
| | |
| | 6) P-1: SHOW THE REQUIRED CLEARANCES FROM THE POOL |
| | HEATER TO THE BEDROOM #2 WINDOW- SECTION G2427.8 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |