| Plan Review Notes For Permit 21010114 |
| Permit Number |
21010114 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-05 15:58:02 | 1ST REVIEW FBC-2020 RES. | | | PERMIT- 21010114 | | | 4/5/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS RISER: PLEASE UPDATE THE FBC 2017 CODE | | | REFERENCES TO THE CURRENT FBC 2020. | | | | | | 2) GAS RISER: PLEASE CORRECT THE 432,000 BTU GENERATOR | | | LOAD TO 306,000 BTUS AS LISTED IN THE SUBMITTED | | | GENERATOR SPECS- SECTION 107.2.1 WPB. | | | | | | 3) SURVEY: PLEASE CORRECT THE 5' GENERATOR DISTANCE | | | FROM OPENINGS TO10' IN COMPLIANCE WITH R305.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|