| 2021-03-23 07:39:26 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD DRAWING REFERENCES THE FBC SIXTH | | | EDITION (2017) AND ASCE 7-10. THE FBC SEVENTH EDITION | | | (2020) WENT INTO EFFECT ON DECEMBER 31, 2020 AND | | | REFERENCES ASCE 7-16. ALL NEW PERMITS APPLIED FOR ON OR | | | AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND | | | REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE 7-16. | | | FS CHAPTER 553 | | | | | | 2) THE NOTES ON THE SURVEY INDICATE THAT THE GENERATOR | | | IS TO BE LOCATED 5 FEET FROM WINDOWS. THE GENERATOR | | | EXHAUST IS REQUIRED TO BE 10 FEET FROM ANY OPENINGS | | | INTO A STRUCTURE. FBC-R303.5.1 MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 3) A VERIFIABLE DIGITAL SIGNATURE IS REQUIRED ON | | | ELECTRONICALLY SUBMITTED DRAWINGS. SEE SIGNATURE REVIEW | | | COMMENTS. | | | | | | |
|