| 2021-03-24 16:51:52 | 1ST REVIEW FBC- 2020 PLUMBING |
| | PERMIT- 21010157 |
| | 1/20/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3.0: THE FINISH SCHEDULE SHOWS GYPSUM WALL |
| | BOARD AND EPOXY PAINT FOR THE NEW MOP SINK WALL |
| | SURROUND WHICH IS NOT CODE COMPLIANT. PLEASE REFER TO |
| | SECTION 1210.2.2 FBC B: WALLS AND PARTITIONS WITHIN 2 |
| | FEET OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL |
| | HAVE SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF |
| | NOT LESS THAN 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. |
| | |
| | 2) P-0.1: PLEASE PROVIDE A SLAB REPAIR DETAIL FOR THE |
| | NEW MOP SINK DRAIN INSTALLATION- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |