| Plan Review Notes For Permit 21010082 |
| Permit Number |
21010082 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-31 13:19:35 | OFFICE BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW WALL AT THE MOP SINK TO COMPLY WITH FBC | | | 1210.2.2 WALLS AND PARTITIONS. | | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR | | | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS | | | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | | MOISTURE. | | | |
|