| 2021-01-20 10:05:57 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | "NEW 2017 NEC CODE CHANGES" #1, AND #2 |
| | |
| | 1) OUTLETS IN COMMON AREAS OF OFFICE AREAS TO BE TAMPER |
| | RESISTANT, SEE THE FOLLOWING SECTION OF ALL THE |
| | LOCATIONS FOR COMMERCIAL OCCUPANCIES.#5 AND #6 |
| | |
| | 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND |
| | 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE |
| | RECEPTACLES IN THE AREAS SPECIFIED IN 406.12(1) THROUGH |
| | (7) SHALL BE LISTED TAMPER-RESISTANT RECEPTACLES. |
| | (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS |
| | (3) CHILD CARE FACILITIES |
| | (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES |
| | (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE |
| | LIKE IN CLINICS, MEDICAL AND DENTAL OFFICES AND |
| | OUTPATIENT FACILITIES |
| | (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2 |
| | TO INCLUDE PLACES OF WAITING TRANSPORTATION, |
| | GYMNASIUMS, SKATING RINKS, AND AUDITORIUMS |
| | (7) DORMITORIES |
| | |
| | |
| | 2) MEETING ROOOM TO HAVE FLOOR RECEPTACLES INSTALLED TO |
| | MEET 210.71(B) |
| | |
| | 210.71(B)(2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM |
| | THAT IS AT LEAST 3.7 M (12 FT) WIDE AND THAT HAS A |
| | FLOOR AREA OF AT LEAST 20 M2 (215 FT2) SHALL HAVE AT |
| | LEAST ONE RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A |
| | DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL |
| | FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR |
| | SPACE. |
| | |
| | 3) RISER DIAGRAM SHOWS #4 TO TRANSFORMER BUT THE PANEL |
| | SCHEDULE "H" SHOWS #6 PLEASE FIX. |