2021-01-13 09:38:17PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2:
  
 1) PLEASE CORRECT & CLARIFY THE INFORMATION IDENTIFIED
 ON THE NEMO REPORT. THE SYSTEM CHOSEN IS W-5 OPEN, IT
 APPEARS THAT THIS IS AN ENCLOSED ROOF STRUCTURE AND
 SHOULD BE CHANGED TO ENCLOSED.
 2) PLEASE PROVIDE INFORMATION AS TO THE TERMINATION OF
 ROOFING MATERIAL AT THE PARAPET WALLS.