| Plan Review Notes For Permit 21010017 |
| Permit Number |
21010017 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-01-21 09:14:42 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVALS DO NOT HAVE A SHOP REVIEW | | | APPROVAL STAMP FROM THE ENGINEER, HOWEVER, THE ENGINEER | | | SIGNED AND SEALED THE RESPONSE LETTER WHICH LISTS THE | | | PRODUCT NOA NOS. FOR THE SLIDING GLASS DOORS AND THE | | | THE SINGLE HUNG WINDOW. THIS WOULD BE SUFFICIENT EXCEPT | | | THAT THE NOA NUMBER IN THE LETTER (NOA NO. 19-0230.05) | | | DOES NOT MATCH THE ONE THAT WAS SUBMITTED(NOA NO. | | | 19-0130.05). PLEASE REVISE THE LETTER OR SUBMIT THE | | | CORRESPONDING PRODUCT APPROVAL. FBC 107.2.1 | | | | | | 2) PROVIDE CLARIFICATION FOR THE BUTT WELD FOR THE | | | CORNER COLUMN REPAIR ON PAGE 140 OF THE DRAWINGS. THE | | | WELD IS SPECIFIED AS 1/16" ON 1/4" MATERIAL, SHOULDN'T | | | THE MINIMUM WELD BE AT LEAST 3/16"? FBC 107.2.1 | | | | | | |
|