2021-01-21 09:14:42PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS DO NOT HAVE A SHOP REVIEW
 APPROVAL STAMP FROM THE ENGINEER, HOWEVER, THE ENGINEER
 SIGNED AND SEALED THE RESPONSE LETTER WHICH LISTS THE
 PRODUCT NOA NOS. FOR THE SLIDING GLASS DOORS AND THE
 THE SINGLE HUNG WINDOW. THIS WOULD BE SUFFICIENT EXCEPT
 THAT THE NOA NUMBER IN THE LETTER (NOA NO. 19-0230.05)
 DOES NOT MATCH THE ONE THAT WAS SUBMITTED(NOA NO.
 19-0130.05). PLEASE REVISE THE LETTER OR SUBMIT THE
 CORRESPONDING PRODUCT APPROVAL. FBC 107.2.1
  
 2) PROVIDE CLARIFICATION FOR THE BUTT WELD FOR THE
 CORNER COLUMN REPAIR ON PAGE 140 OF THE DRAWINGS. THE
 WELD IS SPECIFIED AS 1/16" ON 1/4" MATERIAL, SHOULDN'T
 THE MINIMUM WELD BE AT LEAST 3/16"? FBC 107.2.1
  
  