| 2021-01-11 12:18:53 | A REVISED GAS RISER HAS BEEN SUBMITTED, REVIEWED AND |
| | APPROVED BY T.LARGE. |
| 2021-01-08 09:13:26 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21010015 |
| | 1/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: |
| | |
| | A) PLEASE PROVIDE THE MEASUREMENT OF EACH HORIZONTAL |
| | SECTION OF PE PIPING, AND EACH CUT SECTION OF |
| | GALVANIZED PIPING FROM THE PE TRANSITION AT GROUND- |
| | VERTICALLY TO THE ROOF OF THE BUILDING- AND ACROSS THE |
| | ROOF OF THE BUILDING TO THE BOILER- SECTION 402.4.1 FBC |
| | FG. |
| | |
| | B) BASED ON THE INDIVIDUAL LOADS SHOWN ON THE RISER, |
| | CORRECT THE TOTAL BTU LOAD TO INDICATE 1,160,000 BTU- |
| | SECTION 402.2 FBC FG. |
| | |
| | C) LIST THE PIPE SIZING TABLES ON THE PLAN- SECTION |
| | 402.4.1 FBC FG. BASED ON TABLE 402.4(22) THE 1-1/4 PE |
| | PIPE IS SLIGHTLY UNDERSIZED TO SUPPLY THE TOTAL LOAD. |
| | THE TABLE INDICATES A MAXIMUM LOAD OF 1020 CFH |
| | (1,020,000 BTU) FOR 1-1/4 PIPE AT 870 FT TOTAL |
| | DEVELOPED LENGTH. IT APPEARS A 1-1/2 IN. PE PIPE WILL |
| | BE REQUIRED. |
| | |
| | D) LABEL THE POOL HEATERS AND BOILER AS NEW OR |
| | EXISTING. PLEASE NOTE THAT THE INSTALL MANUALS FOR THE |
| | EQUIPMENT SHALL BE ONSITE AT TIME OF INSPECTION TO |
| | ENSURE PROPER REGULATOR AND GAS PIPING CONNECTIONS PER |
| | MANUFACTURER'S GUIDELINES- SECTION 301.3, 301.5, & |
| | 305.1 FBC FG. |
| | |
| | 2) REGULATORS: PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE NEW MARKED OR HIGHLIGHTED TO |
| | SHOW THE SELECTED MAKES AND MODELS, INPUT AND OUTPUT |
| | PIPE SIZES AND PRESSURES, AND ORIFICE SIZES- SECTION |
| | 410.2 (1) FBC FG. |
| | A) SHOW ON THE RISER THE REQUIRED PIPE UNIONS FOR THE |
| | GALVANIZED PIPING WITHIN 1 FT. OF EITHER SIDE OF THE |
| | REGULATOR. |
| | |
| | 3) PLEASE PROVIDE A BASIC SITE PLAN DRAWING SHOWING THE |
| | PIPING RUN FROM THE METER TO THE POOL HEATERS AND TO |
| | THE BOILER ON THE ROOF. SHOW WHERE THE EXISTING SLEEVES |
| | ARE ON THE PLAN, SLEEVE LENGTHS, AND THE BURIAL DEPTHS |
| | OF THE SLEEVES AND THE NEW UNDERGROUND PE- SECTIONS |
| | 404.12 & 404.12.1 FBC FG. INDICATE A YELLOW INSULATED |
| | COPPER TRACER WIRE OR OTHER APPROVED CONDUCTOR WILL BE |
| | INSTALLED ADJACENT TO THE UNDERGROUND PE- SECTION |
| | 404.17. 3 FBC FG. |
| | |
| | 4) PROVIDE PIPING SUPPORT DETAILS FOR THE GALVANIZED |
| | PIPING RUNNING UP THE BUILDING AND ACROSS THE ROOF |
| | SURFACE IN ACCORDANCE WITH SECTIONS 404.9 & 407.2 FBC |
| | FG. PLEASE NOTE THAT PIPE HANGERS AND SUPPORTS SHALL |
| | CONFORM TO THE REQUIREMENTS OF MSS SP-58 AND SHALL BE |
| | SPACED IN ACCORDANCE WITH SECTION 415.1 INTERVALS OF |
| | SUPPORTS. |
| | |
| | 5) INDICATE HOW THE GALVANIZED PIPING WILL BE PROTECTED |
| | AGAINST CORROSION FROM MOISTURE- SECTION 404.11 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |