| 2021-05-14 09:23:38 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21010007 |
| | 5/14/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC RES- FLORIDA RESDIENTIAL CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY- |
| | SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE |
| | VILLAS. A COMPLETE REVIEW OF THE PLUMBING SYSTEMS WILL |
| | NOT BE ACCOMPLISHED AT THIS TIME. PLEASE REVIEW THE |
| | COMMENTS BELOW AND RESUBMIT CORRECTED PLANS. |
| | |
| | 1) SHEETS P201, P301, P501: REFERENCES ARE MADE FOR |
| | CIVIL PLANS THAT ARE SHOWING POINTS OF CONNECTIONS TO |
| | WATER, SEWER AND STORM DRAIN MAINS, AND LOCATIONS OF |
| | WATER METERS, PREVENTERS ETC. THIS IS THE 2ND REQUEST |
| | FOR THE PLANS- SECTION 107.2.1 WPB. |
| | 2) PLEASE REVIEW ZONING AND BUILDING COMMENTS REGARDING |
| | SITE PLANNING, ADDRESSING AND SEPARATE PERMITTING. A |
| | COMPLETE PLUMBING APPROVAL FOR THE VILLA FOUNDATIONS |
| | CANNOT BE COMPLETED AT THIS TIME- SECTION 107.2.1 WPB. |
| | |
| | 3) SHEET P201 SANITARY RISER: THE 3-INCH WASHING |
| | MACHINE DRAIN CANNOT CONNECT TO THE FIXTURE DRAIN OF |
| | THE WATER CLOSET, AND SHALL CONNECT TO THE BUILDING |
| | DRAIN INDEPENDENTLY AT A POINT EITHER DOWNSTREAM OF THE |
| | HORIZONTAL WET VENT FOR THE POWDER ROOM- SECTION 912.1 |
| | FBC P. |
| | |
| | 4) P201 SANITARY RISER: THE VENT FOR THE SHOWER IN BATH |
| | 2 IS NOT SHOWN- SECTION 910.1 FBC P. PLEASE NOTE THAT |
| | THIS IS AN ADVISORY COMMENT AND THE ENTIRE PLUMBING |
| | SYSTEM IS NOT BEING REVIEWED AT THIS TIME. |
| | |
| | 5) P101 & P201: SHOW THE WATER HEATER PAN DRAIN LINE |
| | RUNS AND DISCHARGE LOCATIONS. PLEASE INDICATE THE TYPE |
| | AND SIZE OF PIPES- SECTIONS 504.7.1 AND 504.7.2 FBC P. |
| | |
| | 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |