| 2021-05-13 16:03:53 | THE PREVIOUS FIRE COMMENTS WERE NOT SPECIFICALLY |
| | ADDRESSED. |
| | |
| | THE PERMIT WILL BE APPROVED WITH THE PREVIOSU COMMENTS |
| | AS PROVISO THAT WILL REQUIRE A DETAILED RESPONSE, UNDER |
| | THE CONSTRUCTION SUBMITTAL OF THE STRUCTURE, TO EACH |
| | QUESTION ANDD/OR THE APPLICABLE SHEET PAGE THAT |
| | ADDRESSES THE COMMENT. |
| | |
| | |
| | THE PREVIOUS COMMENTS ARE LIST BELOW: |
| | |
| | FIRE HAS NO OBJECTION TO A FOUNDATION PERMIT; THE BELOW |
| | COMMENTS ARE MORE RELATED TO THE OCCUPANCY |
| | CLASSIFICATION AND IF A LIFE SAFETY REVIEW IS REQUIRED |
| | UNDER THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 1) SHEET A000 - WITHIN THE SECTION TITLED DESIGN |
| | PARAMETERS, THERE IS AN INDICATION OF FBC GROUP R-1 |
| | TWO-STORY DUPLEX. |
| | |
| | FOR CLARIFICATION PURPOSES, PER THE FLORIDA FIRE |
| | PREVENTION CODE ARE THESE CONSIDERED A TWO-FAMILY |
| | DWELLING PER NFPA 101 CH 24....OR ARE THEY ASSOCIATED |
| | WITH THE PROPOSED HOTEL AND BE RENTED OUT TO CLIENTS |
| | THUS COMPLYING WITH CH 28. |
| | |
| | 3.3.145* HOTEL. A BUILDING OR GROUPS OF BUILDINGS UNDER |
| | THE SAME |
| | MANAGEMENT IN WHICH THERE ARE SLEEPING ACCOMMODATIONS |
| | FOR MORE |
| | THAN 16 PERSONS AND PRIMARILY USED BY TRANSIENTS FOR |
| | LODGING WITH OR |
| | WITHOUT MEALS. |
| | |
| | 28.1.1.5 THE TERM HOTEL, WHEREVER USED IN THIS CODE, |
| | SHALL INCLUDE |
| | A HOTEL, AN INN, A CLUB, A MOTEL, A BED AND BREAKFAST, |
| | OR ANY OTHER |
| | STRUCTURE MEETING THE DEFINITION OF HOTEL. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS. |
| | |
| | |
| | |
| | 2) SHOULD THIS BE CLASSIFIED AS AHOTEL OCCUPANCY A FIRE |
| | SPRINKLER SYTEM IS REQUIRED. |
| | |
| | 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH 28.3.5.3. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS AND EOR DOCUMENTS PER |
| | F.A.C. 69G WITH THIS MASTER |
| | |
| | |
| | |
| | 3) SHOULD THIS BE CLASSIFIED AS AHOTEL OCCUPANCY A FIRE |
| | ALARM SYTEM IS REQUIRED. |
| | |
| | 28.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 28.3.4.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE |
| | WITH SECTION |
| | 9.6, EXCEPT AS MODIFIED BY 28.3.4.2 THROUGH 28.3.4.6, |
| | SHALL BE |
| | PROVIDED. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS WITH THIS MASTER. |
| | |
| | |
| | 4) SHOULD THIS BE CLASSIFIED AS A HOTEL OCCUPANCY AND |
| | WITH AN ATTACHED GARAGE |
| | |
| | 28.3.4.6 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE |
| | DETECTION SYSTEMS. |
| | 28.3.4.6.1 CARBON MONOXIDE ALARMS OR CARBON MONOXIDE |
| | DETECTORS |
| | IN ACCORDANCE WITH SECTION 9.8 AND 28.3.4.6 SHALL BE |
| | PROVIDED IN |
| | NEW HOTELS AND DORMITORIES WHERE EITHER OF THE |
| | FOLLOWING |
| | CONDITIONS EXISTS: |
| | (1) GUEST ROOMS OR GUEST SUITES WITH COMMUNICATING |
| | ATTACHED |
| | GARAGES, UNLESS OTHERWISE EXEMPTED BY 28.3.4.6.3 |
| | (2) GUEST ROOMS OR GUEST SUITES CONTAINING A |
| | PERMANENTLY |
| | INSTALLED FUEL-BURNING APPLIANCE OR FUEL-BURNING |
| | FIREPLACE |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS WITH THIS MASTER. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |